Wash. Admin. Code § 173-160-211
TABLE 3
Recommended Well Diameters
| AnticipatedWell Yieldin gpm | Nominal Sizeof Pump Bowlsin inches | Optimum Sizeof Well Casingin inches | |||
| Less than 100 | 4 | 6 ID | |||
| 75 to 175 | 5 | 8 ID | |||
| 150 to 350 | 6 | 10 ID | |||
| 300 to 700 | 8 | 12 ID | |||
| 500 to 1000 | 10 | 14 OD | |||
| 800 to 1800 | 12 | 16 OD | |||
| 1200 to 3000 | 14 | 20 OD | |||
| 2000 to 3800 | 16 | 24 OD | |||
| 3000 to 6000 | 20 | 30 OD |