9 Va. Admin. Code § 25-790-120
B. Final engineering documents. Drawings, plans, specifications and other engineering documents that are submitted to the area engineer for a technical evaluation shall be in substantial compliance with this chapter prior to issuance of a CTC by the director. Engineering documents may be submitted by the owner to the area engineer following the preliminary engineering conference, or following a technical evaluation of the preliminary engineering proposal if required. Up to four copies shall be submitted to the area engineer for non-Virginia Revolving Loan Fund funded projects and up to five copies shall be submitted for projects financed through the Virginia Revolving Loan Fund. The original of the letter of submittal with appropriate signature(s) shall accompany the engineering documents. The letter of submittal should identify any necessary actions to be taken by the area engineer to expedite evaluation of the submitted documents.
All drawings, specifications, engineer's reports and other documents submitted for evaluation shall be prepared by or under the supervision of appropriately licensed professionals, legally qualified to practice in Virginia, in accordance with the provisions of §§ 54.1-400 to 54.1-411 of the Code of Virginia inclusive.
All submitted plans for sewerage systems or treatment works shall bear a suitable title showing the name of the municipality, sewer district, institution or other owner and shall show the scale in feet, a graphical scale, the north point, date and the name of the appropriate licensed professional. Also, each plan sheet shall bear the same general title identifying the overall project, and each shall be numbered. Appropriate subtitles shall be included on the individual sheets. The plans shall be clear and legible. They shall be drawn to a scale that will permit all necessary information to be plainly shown. The size of the plans should be no larger than 36 inches by 48 inches. The datum used should be indicated. Locations of all special features, when made, shall be shown on the plans. Logs of test borings should be given either on plans or in the specifications. Detail plans shall consist of plan views, elevations, sections, and supplementary views which, together with the specifications and general layouts, provide the working information for the contract and construction of the works. The plans shall include dimensions and relative elevations of structures, the location and outline form of equipment, location and size of piping, water levels, ground elevations, and erosion control abatement facilities. Data shall be provided for proposed additions of flow to existing sewerage systems indicating that the additional sewage flow from the proposed project will have no adverse impact on the operation of downstream facilities.
C. Sewerage systems. Plans submitted for new construction or substantial modification (increasing flow capacity by more than 25%) of sewage collection piping shall include the following: the location, size, type and direction of flow of all existing and proposed sanitary sewers involved in the project.
1. Detailed plans when submitted for evaluation shall provide complete and properly scaled graphical depictions of design information. Profiles shall have a horizontal scale of not more than 100 feet to the inch and a vertical scale of not more than 10 feet to the inch. The plan view shall be drawn to a corresponding horizontal scale. Plans and profiles shall show:
4. Special detail drawings, made to a scale to clearly show the nature of the design, shall be furnished to show the following particulars:
D. Sewage pumping stations. Plans submitted for technical evaluation involving new construction or substantial modification (increasing flow capacity by more than 25%) of pumping stations shall address the following design information: (i) the location and extent of the tributary area; (ii) the location of municipal boundaries within the tributary area; and (iii) the location of the pumping station and force main and pertinent elevations.
2. Detailed plans submitted for evaluation shall provide the following design information where applicable:
E. Treatment works. Plans submitted for technical evaluation of projects involving new construction or substantial modifications (increasing flow capacity by more than 25%) of treatment works shall identify the treatment works relative to the remainder of the system. For new construction, the plan shall include sufficient topographic features to indicate its location relative to streams and the point of discharge of treated effluent. Also the forms of land use (commercial, residential, and agricultural, existing or proposed) and access controls for the near future over a 700-foot radius from the proposed treatment works structures must be indicated. Existing buildings and their type of use within 700 feet of the new treatment works site shall be adequately described, e.g., by means of topographic maps, aerial photos, drawings, etc.
1. For technical evaluation, the proposed treatment works design submittal shall include the following as specified:
2. For technical evaluation, detailed plans shall include the following:
3. Facility closure plans shall address the following information as a minimum:
F. Plans submitted for technical evaluation of biosolids use facilities, including substantial modifications (new location of storage on site, or increasing design capacity by more than 20%) from that previously approved shall identify the proposed locations, management practices, biosolids sources, treatment and quality information as required. For new construction, the plan shall include sufficient topographic features to indicate its location relative to streams and other land use facilities, as required. The forms of land use (commercial, residential, and agricultural existing or proposed) buffer zones and access controls, for the near future, surrounding the proposed biosolids use facilities must be indicated. Existing buildings and their type of use within 200 feet of the new site shall be adequately described (e.g., by means of topographic maps, aerial photos, drawings, etc.).
5. Proposed land use (postclosure) of site.
.G. Approval. The area engineer will approve or disapprove the construction drawings and notify the owner in accordance with 9VAC25-790-80 C.
Facility closure plans shall address the following information as a minimum:
§ 62.1-44.15 of the Code of Virginia.
Former 12VAC5-581-170 derived from Virginia Register Volume 18, Issue 10, eff. February 27, 2002; amended and adopted as 9VAC25-790-120, Virginia Register Volume 20, Issue 9, eff. February 12, 2004; amended, Virginia Register Volume 24, Issue 6, eff. January 1, 2008.