9 Va. Admin. Code § 25-580-60
1. Alternatives allowed. All existing UST systems must comply with one of the following requirements:
2. Tank upgrading requirements. Steel tanks must be upgraded to meet one of the following requirements in accordance with a code of practice developed by a nationally recognized association or independent testing laboratory:
a. Interior lining. Tanks upgraded by internal lining must meet the following:
b. Cathodic protection. Tanks upgraded by cathodic protection must meet the requirements of 9VAC25-580-50 1 b (2), (3), and (4) and the integrity of the tank must have been ensured using one of the following methods:
c. Internal lining combined with cathodic protection. Tanks upgraded by both internal lining and cathodic protection must meet the following:
(2) The cathodic protection system meets the requirements of subdivisions 1 b (2), (3), and (4) of 9VAC25-580-50.
(d) American Petroleum Institute Recommended Practice 1632, Cathodic Protection of Underground Petroleum Storage Tanks and Piping Systems.
NOTE: The following codes of practice may be used to comply with the periodic lining inspection requirement in subdivision 2 a (2) of this section:
NOTE: The following historical codes of practice were listed as options for complying with subdivision 2 of this section:
3. Piping upgrading requirements. Metal piping that routinely contains regulated substances and is in contact with the ground must be cathodically protected in accordance with a code of practice developed by a nationally recognized association or independent testing laboratory and must meet the requirements of subdivisions 2 b (2), (3) and (4) of 9VAC25-580-50.
NOTE: The codes of practice listed in the note following subdivision 2 b of 9VAC25-580-50 may be used to comply with this requirement.
Owners and operators must permanently close in accordance with Part VII (9VAC25-580-310 et seq.) of this chapter any UST system that does not meet the new UST system performance standards in 9VAC25-580-50 or has not been upgraded in accordance with subdivisions 2, 3, and 4 of this section. This does not apply to previously deferred UST systems described in Part X (9VAC25-580-380 et seq.) of this chapter and where an upgrade is determined to be appropriate by the department.
Owners and operators must obtain a permit and the required inspections in accordance with the provisions of the Virginia Uniform Statewide Building Code (§ 36-97 et seq. of the Code of Virginia).
A permit from the building official must be obtained prior to upgrading any UST system. No upgraded UST system shall be placed into use unless and until the system is inspected in accordance with the provisions of the Virginia Uniform Statewide Building Code (§ 36-97 et seq. of the Code of Virginia).
In the case of state-owned facilities, the Department of General Services shall function as the building official in accordance with § 36-98.1 of the Code of Virginia.
In the case of federal facilities the building official must be contacted. Owners and operators must obtain a permit and the required inspections in accordance with the provisions of the Virginia Uniform Statewide Building Code (§ 36-97 et seq. of the Code of Virginia).
§§ 62.1-44.15 and 62.1-44.34:9 of the Code of Virginia; 42 USC § 6901 et seq.; 40 CFR Parts 280 and 281.
Derived from VR680-13-02 § 2.2, eff. October 25, 1989; amended, Virginia Register Volume 34, Issue 1, eff. January 1, 2018; Errata, 34:4 VA.R. 503 October 16, 2017; amended, Virginia Register Volume 39, Issue 5, eff. November 23, 2022.