Air compressors shall be equipped with automatic temperature activated shutoff mechanisms set for 400°F or with fusible plugs installed in the compressor discharge lines as near the compressors as possible. Fusible plugs shall melt at temperatures 50° less than the flash points of the lubricating oils.