A. No employee shall be permitted to approach or take any conductive object closer to exposed energized parts than shown in subsection B (Table R-2) of this section unless:
B. Approach distances to exposed energized overhead power lines and parts.
| TABLE R-2. Approach Distances to Exposed Energized Overhead Power Lines and Parts. | |
| Voltage range (phase to phase, RMS) | Approach distance (inches) |
| 300 V and less | (1) |
| Over 300 V, not over 750V | 12 |
| Over 750 V not over 2 kV | 18 |
| Over 2 kV, not over 15 kV | 24 |
| Over 15 kV, not over 37 kV | 36 |
| Over 37 kV, not over 87.5 kV | 42 |
| Over 87.5 kV, not over 121 kV | 48 |
| Over 121 kV, not over 140kV | 54 |