- A. The blowdown from a boiler or boilers that enters a sewer system or blowdown which is considered a hazard to life or property shall pass through blowoff equipment that will reduce pressure and temperature as required below.
- B. The temperature of the water leaving the blowoff equipment shall not exceed 140°F.
- C. The pressure of the blowdown leaving any type of blowoff equipment shall not exceed five psig.
- D. The blowoff piping and fittings between the boiler and the blowoff tank shall comply with the current edition of the ASME Code, Section I and ASME B31.1.
- E. All materials used in the fabrication of boiler blowoff equipment shall comply with the current edition of the ASME Code, Section II.
- F. All blowoff equipment shall be fitted with openings to facilitate cleaning and inspection.
- G. Blowoff equipment which conforms to the provisions set forth in the National Board publication, "Boiler Blowoff Equipment", shall meet the requirements of this section.