13 Va. Admin. Code § 5-63-230
A. Change Item 5 of Section 703.2.2 of the IBC to read:
B. Change Section 703.5 of the IBC to read:
703.7 Fire-resistance assembly marking. Where there is a concealed floor, floor-ceiling, attic space, the fire walls, fire barriers, fire partitions, smoke barriers, or any other wall required to have protected openings or penetrations shall be designated above ceilings and on the inside of all ceiling access doors that provide access to such fire rated assemblies by signage having letters no smaller than one inch (25.4 mm) in height. Such signage shall indicate the fire-resistance rating of the assembly and the type of assembly and be provided at horizontal intervals of no more than eight feet (2438 mm).
Note: An example of suggested formatting for the signage would be "ONE HOUR FIRE PARTITION."
C. Add Exception 2 to Section 705.2 of the IBC to read:
D. Change Section 706.1 of the IBC to read:
706.1 General. Each portion of a building separated by one or more fire walls shall be considered a separate building. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Equipment and systems are permitted to serve multiple attached buildings on the same lot where separated by one or more fire walls.
F. Add Exception 4 to Section 706.5.2 of the IBC to read:
G. Change Section 716.2.1.4 of the IBC to read:
716.2.1.4 Smoke and draft control. Fire door assemblies located in smoke barrier walls shall also meet the requirements for a smoke and draft control door assembly tested in accordance with UL 1784.
H. Change Section 717.5.3 of the IBC to read:
717.5.3 Shaft enclosures. Shaft enclosures that are permitted to be penetrated by ducts and air transfer openings shall be protected with approved fire and smoke dampers installed in accordance with their listing.
Exceptions:
I. Add Section 717.6.2.2 to the IBC to read:
717.6.2.2 Equipment shutdown. Where ceiling radiation dampers are listed as static dampers, the HVAC equipment shall be effectively shut down to stop the airflow prior to the damper closing using one of the following methods:
§ 36-98 of the Code of Virginia.
Derived from Virginia Register Volume 22, Issue 3, eff. November 16, 2005; amended, Virginia Register Volume 24, Issue 14, eff. May 1, 2008; Volume 27, Issue 2, eff. March 1, 2011; Change in Effective Date, 27:5 VA.R. 534 November 8, 2010; amended, Virginia Register Volume 30, Issue 16, eff. July 14, 2014; Volume 34, Issue 18, eff. September 4, 2018; Volume 37, Issue 14, eff. July 1, 2021; Volume 40, Issue 9, eff. January 18, 2024.