12 Va. Admin. Code § 5-635-320
A. The owner of a rainwater harvesting system shall ensure that the rainwater harvesting system is inspected by an operator in accordance with Table 5.
| TABLE 5 Minimum operator visit frequency for rainwater harvesting systems | ||
| End Use Tier | Initial Inspection | Regular Inspection Schedule |
| 1 | Prior to the system entering service | As needed |
| 2, 3 | Prior to the system entering service | Every 12 months while structure is occupied. If system only provides water for outdoor use, then as needed |
| 4 (single service connection) | Condition of issuance of operation permit | Every 180 calendar days while structure is occupied* |
| 4 (multiple service connections) | Condition of issuance of operation permit | Every 90 calendar days while any connection serves an occupied structure* |
| *If a structure is vacant longer than the regular inspection cycle in Table 5, an operator shall inspect the rainwater harvesting system prior to the structure becoming reoccupied. |
§§ 32.1-12 and 32.1-248.2 of the Code of Virginia.
Derived from Virginia Register Volume 41, Issue 5, eff. November 20, 2024.