A. A rainwater harvesting system shall be designed, installed, and maintained to prevent contamination of secondary water supplies by backflow. Backflow prevention shall be achieved by one or more of the following:
- 1. Backflow elimination methods, including air gap separation or physical disconnection;
- 2. Backflow prevention assemblies, including the reduced pressure principle, double check valve, and pressure vacuum breaker assemblies; or
- 3. If backflow prevention is not generally required to withstand continuous pressure over 12 hours or to control high hazards, a backflow prevention device, including atmospheric type vacuum breakers and dual check valve devices.
- B. Backflow prevention assemblies and backflow prevention devices shall be suitable to the application and shall conform to the USBC.
Statutory Authority
§§ 32.1-12 and 32.1-248.2 of the Code of Virginia.
Historical Notes
Derived from Virginia Register Volume 41, Issue 5, eff. November 20, 2024.