- A. The station and its piping and valving arrangement shall be designed to prevent unauthorized use, tampering, and vandalism.
- B. An air gap or RPZ assembly shall be provided on the potable water fill connection to prevent backflow into the waterworks.
- C. The piping and valving arrangement shall prevent contaminants from being transferred from a hauling tank or vessel to others subsequently using the water loading station.
- D. Hoses used to fill potable water tanks and vessels shall be approved for potable water contact.
- E. Hoses shall not come into contact with the ground or other contaminated surface and shall otherwise be handled, maintained, and stored in a manner to prevent contamination.