A. The minimum size pipe for water distribution mains shall be four inches in diameter. Pipes of lesser diameter may be used in the following instances:
- 1. When the run is less than 300 feet, two-inch diameter pipe may be used.
- 2. When the run is less than 600 feet but more than 300 feet, three-inch diameter pipe may be used.
- 3. Any departure in sizing shall be justified by hydraulic analysis and future water demands.
- B. Fire hydrants shall not be connected to water mains that are not designed to carry fire flows. Connection of a fire hydrant to a pipe of less than six inches in diameter is prohibited.
- C. Where a noncommunity waterworks serves a single building, the plumbing shall be in accordance with the USBC. Where a noncommunity waterworks serves two or more buildings, the pipe shall be of sufficient size to provide adequate flow and pressure in order to meet the system demands.
Statutory Authority
§ 32.1-12 and 32.1-170 of the Code of Virginia.
Historical Notes
Derived from VR355-18-012.02 § 3.49, eff. August 1, 1991; amended, Virginia Register Volume 37, Issue 20, eff. June 23, 2021.