12 Va. Admin. Code § 5-590-376
B. Turbidity measurements shall be performed on representative samples of the filtered water every four hours (or more frequently) that the waterworks serves water to the public. The owner may substitute continuous turbidity monitoring for grab sample monitoring if the owner validates the continuous measurement for accuracy on a regular basis using a protocol approved by the department. For a waterworks using slow sand filtration or filtration treatment other than conventional treatment, direct filtration, or diatomaceous earth filtration, the department may reduce the sampling frequency to once per day if the department determines that less frequent monitoring is sufficient to indicate effective filtration performance. For a waterworks serving 500 or fewer persons, the department may reduce the turbidity sampling frequency to once per day, regardless of the type of filtration treatment used, if the department determines that less frequent monitoring is sufficient to indicate effective filtration performance.
C. The residual disinfectant concentration of the water entering the distribution system shall be monitored continuously, and the lowest and highest values shall be recorded each day. If there is a failure in the continuous monitoring equipment, then grab sampling every four hours shall be conducted instead of continuous monitoring, but such grab sampling shall be conducted for no more than five working days following the failure of the equipment. The owner of a waterworks serving 3,300 or fewer persons may collect grab samples instead of continuous monitoring on an ongoing basis at the frequencies prescribed in Table 376.1.
3. If at any time the residual disinfectant concentration falls below 0.2 mg/L in a waterworks using grab sampling instead of continuous monitoring, then the owner shall collect a grab sample every four hours until the residual disinfectant concentration is equal to or greater than 0.2 mg/L.
| TABLE 376.1 Grab Sample Monitoring Frequency | |
| WATERWORKS SIZE BY POPULATION | SAMPLES/DAY |
| 500 or less | 1 |
| 501 - 1,000 | 2 |
| 1,000 - 2,500 | 3 |
| 2,501 - 3,300 | 4 |
E. The following information on the samples collected in the distribution system in conjunction with total coliform monitoring pursuant to 12VAC5-590-395 A 2 shall be reported monthly to the department by the owner:
6. For the current and previous month the waterworks serves water to the public, the value of "V," in percent, in the following formula:
V = [(c + d + e) / (a + b)] X 100
where
a = the value in subdivision E 1 of this section;
b = the value in subdivision E 2 of this section;
c = the value in subdivision E 3 of this section;
d = the value in subdivision E 4 of this section;
e = the value in subdivision E 5 of this section.
§§ 32.1-12 and 32.1-170 of the Code of Virginia.
Derived from Virginia Register Volume 37, Issue 20, eff. June 23, 2021.