Va. Code Ann. § 62.1-44.34:34
B. The owner or operator of any facility, including facilities described in § 62.1-44.34:32, that (i) discharges industrial wastewater pursuant to an industrial pretreatment program permit into the sewer collection system of a major publicly owned treatment works that discharges into the Occoquan Reservoir, the Occoquan River, Bull Run, or any of their tributaries above the Occoquan Reservoir or (ii) discharges industrial wastewater or industrial stormwater directly into the Occoquan Reservoir, the Occoquan River, Bull Run, or any of their tributaries above the Occoquan Reservoir pursuant to an individual VPDES permit issued by the Department shall monitor for PFAS using EPA Method 1633 or an alternative method approved by the EPA beginning on or before October 1, 2025.
The owner or operator of any such facility shall perform representative monitoring of its wastewater or stormwater discharges, as applicable, for PFAS at least once every three months unless the Department authorizes the owner or operator of a facility with proper monitoring results that are below the method detection level for four consecutive quarters to reduce or discontinue monitoring. The owner or operator of a facility shall make a good faith effort to obtain the results of such monitoring from the laboratory within 45 days of the sampling date or within the shortest practicable time thereafter. The owner or operator of a facility shall report all results to the Department no later than the tenth day of the next month after the month in which the result is reported by the laboratory. This report shall include all such PFAS analytes measured by the test method.
2025, c. 650.