(3) Light intensity shall be at or above the minimum foot-candle in accordance with Table 4. Values in table 4 are minimum maintained average illuminance measured at the task plane. Areas not shown in Table 4, including parking lots and approaches to the building, shall have fixtures to provide light levels as recommended in IES Recommended Practice RP-20-1998, Lighting for Parking Facilities by the Illuminating Engineering Society of North America, which is adopted and incorporated by reference.
TABLE 4
Assisted Living Facilities Lighting Standards
Physical Plant Area Minimum Foot-candle
Corridors
Day 15
Night 7.5
Exits 15
Stairways 15
Res. Room
General 7.5
Reading/Mattress Level 30
Toilet area 30
Lounge
General 7.5
Reading 30
Recreation 30
Dining 20
Dining and Recreation 30
Laundry 30
KEY: health care facilities
Date of Last Change: August 20, 2018
Notice of Continuation: January 23, 2023
Authorizing, and Implemented or Interpreted Law: 26-21-5; 26-21-16