Utah Admin. Code R432-12-5
(1) Table 1 identifies the levels of care and construction requirements that apply.
TABLE 1CONSTRUCTION REQUIREMENTS SUMMARYLEVEL ILEVEL IILEVEL IIILEVEL IVNumber of. residents1-164-164-164-16Are residents Capable of Unassisted Self Preservation?No, they are non ambulatory non-mobileNo, they are non ambulatory non-mobileYes, they are ambulatory mobileYes, they are ambulatory mobile What are resident's exit ability in an emergency Restricted, physical or mental disability and medical conditionRestricted, physical or mental disabilityRestricted, chemical or physical restraintsNot restrictedPercentage of accessible rooms required100%10% or 100% if Physical Rehab.10%10% Construction Requirements code or regulationNFPA 101NFPA 101NFPA 101 Utah Fire Prevention Board Rule R710-3; IBC R-4 occupancyFire rating of construction1 hour1 hour1 hour No requirementSprinkler required?YesYesYesOnly if bldg.. larger than 4,500 SFSmoke detector required?YesYesYesYes
Manual fire alarm required?YesYesYesYesAbove 3 systems required to be interconnectedYesYesYesNoCorridor width required8 feet 6 feet`5 feetAs required by IBCResident room door width required44 inch44 inch36 inch36 inchNurse call system required?YesYesOptionalyes
(8) The licensee shall ensure that:
KEY: health care facilities
Date of Last Change: November 9, 2023
Notice of Continuation: February 28, 2024
Authorizing, and Implemented or Interpreted Law: 26B-2-202