(1) the water supply serving a public pool and any plumbing fixture, including any drinking fountain, hand washing sink, and shower, is designed, installed, and operated according to the requirements set forth by:
- (a) Plumbing Code;
- (b) Title R309; and
- (c) local health department regulations;
- (2) any portion of the water supply, recirculation, and distribution system serving the facility is protected against backflow; and
(3) water introduced into the pool, either directly or through the circulation system, is supplied through a backflow preventer that:
- (a) protects against contamination from back-siphonage or backpressure in accordance with Plumbing Code, such as an air gap or backflow prevention assembly; and
- (b) is not connected to the pool recirculation system on the discharge side of the pool recirculation pump.
- (4) The manager shall ensure that each hose bibb is equipped with a vacuum breaker listed by the International Association of Plumbing and Mechanical Officials (IAPMO), the American Society of Sanitary Engineering (ASSE), or other nationally recognized standard.
The manager shall ensure that:
KEY: pools, spas, swimming, water
Date of Last Change: May 26, 2026
Notice of Continuation: October 21, 2021
Authorizing, and Implemented or Interpreted Law: 26B-1-202; 26B-7-113; 26B-7-124; 26B-7-402