- (1) The manager shall consult with a local health officer during a plan review of a lazy river or action river.
(2) The manager shall ensure that each lazy river or action river:
- (a) meets any applicable requirement of this rule in addition to this section;
- (b) is equipped with means of entry and exit at each 150-foot interval of perimeter or fraction thereof;
- (c) does not allow a handrail, step, stair, or propulsion jet to protrude into the channeled flow of water;
- (d) has a minimum turnover rate of two hours, as described in Table 1; and
- (e) has a minimum number of surface skimmers based on one skimmer for each 500 square feet of surface area or fraction thereof.
(3)(a) The manager shall ensure that a lazy river or action river has a deck that meets the requirements of Subsection R392-302-15(1) provided along at least one side of the channeled flow of water that includes a handhold that meets the requirements of Subsection R392-302-16(1).
(b)(i) If the channel is wider than 15 feet, the manager shall ensure that decking is installed along both sides of the channel.
- (ii) If the channel is 15 feet or less in width, decking is only required on one side of the channel.
(4) A deck obstruction, such as a bridge or landscaping, may be allowed around the perimeter of a lazy river or an action river if:
- (a) lifeguarding, sight lines, or rescue operations are not impaired;
- (b) any obstruction meets the requirements of Subsection R392-302-15(3); and
- (c) water quality is not negatively impacted.
(5) If a bridge spans the width of a lazy river, the manager shall ensure that each bridge has a minimum clearance of:
- (a) seven feet from the pool floor surface of the lazy river or the action river; and
- (b) four feet above the designed water level to any structure overhead.
- (6) The manager shall ensure that any bridge has a barrier on both sides of the bridge that is a minimum of 42 inches in height.
- (7) The manager shall ensure that each lazy river or action river with a booster pump system to create the channeled flow of water meets the requirements of Subsection R392-302-19(8), including jet or water agitation systems.
- (8) The manager shall ensure adequate lighting, as described in Section R392-302-18, when the river passes under a bridge, architectural feature, or other landscaping feature.
KEY: pools, spas, swimming, water
Date of Last Change: May 26, 2026
Notice of Continuation: October 21, 2021
Authorizing, and Implemented or Interpreted Law: 26B-1-202; 26B-7-113; 26B-7-124; 26B-7-402