Utah Admin. Code R317-5-6
B. Minimum separation distance from the bottom of the absorption trenches to the anticipated maximum ground water table is 48 inches. If a mound, sand lined trench, or packed bed pretreatment unit is designed and installed on the LUWD system, the horizontal separation distance may be reduced to 24 inches.
6.2. Components Required in a LUWD System:
C. A pressurized subsurface disposal system.
3. The Utah Guidance for Performance, Application, Design, Operation and Maintenance: Pressure Distribution Systems document shall be used for design requirements, along with the following:
i. All pressure transport, manifold, lateral piping, and fittings shall meet PVC Schedule 40 standards or equivalent.
ii. The ends of lateral piping shall be constructed with sweep elbows or an equivalent method to bring the end of the pipe to the final grade. The ends of the pipe shall be provided with threaded plugs, caps, or other devices acceptable to the division to allow for access and flushing of the lateral.
6.1. Shall meet the requirements of Section R317-4-6, with these exceptions:
KEY: water pollution, large underground wastewater, sewerage, engineering
Date of Last Change: March 26, 2014
Notice of Continuation: April 7, 2022
Authorizing, and Implemented or Interpreted Law: 19-5