- (1) Location. The location for a pump station shall be compatible with the hydraulics of the water system.
(2) Flood Protection and Site Drainage.
- (a) A pump station shall be located at, or protected from, flooding to an elevation of at least three feet above either the 100-year flood or highest recorded flood, whichever is higher.
- (b) The site for a pump station shall be graded to direct surface water drainage away from the pump station.
(3) Pump Station Drainage and Flooding Prohibition. A pump station:
- (a) may not be subject to flooding;
- (b) shall be drained to prevent water from collecting on the floor; and
- (c) shall provide an outlet for drainage from pump glands, air release valves, and other equipment without allowing water to flow across the floor to reach the outlet. See Subsection R309-550-6(6) for clearance requirements for air release vent pipes discharging to floor drains.
(4) Access.
- (a) A pump station shall be accessible.
- (b) Access to a pump station in an underground vault or compartment or between floors of a pump station shall be provided by a permanent stairway, ladder, or ramp.
(5) Construction, Security, and Layout. A pump station shall be:
- (a) weatherproof;
- (b) constructed and maintained to exclude animals;
- (c) locked to prevent unauthorized entry and vandalism; and
(d) sized, configured, and equipped to allow for:
- (i) operation and maintenance; and
- (ii) installation and removal of pumps and other equipment.
(6) Heating. Heating shall be provided if needed:
- (a) for the safe and efficient operation of equipment; and
- (b) to prevent equipment from freezing.
- (7) Lighting. Lighting shall be provided to allow for the operation and maintenance of equipment.
(8) Ventilation.
- (a) Ventilation shall be provided for a pump station.
(b) Forced ventilation of at least six air-changes per hour shall be provided for a pump station:
- (i) in a confined space;
- (ii) in a subsurface compartment or vault;
- (iii) if an unsafe atmosphere may develop.
(9) Wet Wells. A Finished water wet well at a pump station shall:
- (a) be waterproof;
- (b) allow for the removal of water and sediment;
- (c) be covered to protect the water from contamination; and
- (d) have an access opening and a lid that meet the requirements for a water storage tank in Section R309-545-14.
- (10) Return of Used Water to the Drinking Water System Prohibited. Water withdrawn from a public drinking water system for any use may not be returned to the system.
(11) Automatic and Remote-Controlled Stations.
- (a) An automatically operated pump station shall have an automatic signaling apparatus that immediately notifies a water system operator when the station is out of service.
(b) A remote-controlled pump station shall be:
- (i) electrically operated and controlled; and
- (ii) have an automatic signaling apparatus that immediately notifies a water system operator when the station is out of service.
KEY: drinking water, pumps, hydropneumatic systems, individual home booster pumps
Date of Last Change: June 26, 2024
Notice of Continuation: February 10, 2025
Authorizing, and Implemented or Interpreted Law: 19-4-104