(1) Installation in attic spaces.
- (a) Entrance way providing access to equipment shall not be less than the largest piece of equipment to be replaced.
- (b) There shall be a vertical clearance of at least four (4) feet and six (6) inches for use by those conducting necessary examination. In addition there shall be a walkway not less than twenty-four (24) inches wide on the ceiling joist running from the attic opening to the equipment, without an obstruction.
(2) Installation in crawl spaces underneath buildings.
- (a) Entrance way providing access to equipment shall not be less than the largest piece of equipment to be replaced.
- (b) There shall be a vertical clearance of at least four (4’) feet and six (6”) inches unobstructed crawl space to the unit.
- (c) If four (4’) feet and six (6”) inches of clearance cannot be maintained, the unit shall be located no more than twelve (12’) feet from the entrance opening and a clear unobstructed crawl space not less than thirty (30”) inches in height and twenty-four (24”) inches in width shall be maintained.
- (d) Light fixtures in crawl spaces shall have guarded covers.
Authority: T.C.A. §§ 68-102-113, 68-102-143, and 68-102-150. Administrative History: Original rule certified June 10, 1974. Amendment filed October 24, 1974; effective January 17, 1975. Amendment filed April 20, 1978; effective May 22, 1978. Repeal and new rule filed October 27, 1981; effective December 11, 1981. Repeal and new rule filed June 28, 1984; effective July 28, 1984. Repeal and new rule filed March 12, 1987; effective April 26, 1987. Amendment filed June 27, 1990; effective August 11, 1990. Amendment filed September 22, 1993; effective January 28, 1994. Amendment filed November 4, 1996; effective March 7, 1997. Amendment filed November 14, 2008; effective January 28, 2009.