Secondary containment systems required in accordance with § 74:56:03:04 for existing AST systems located at facilities with a total capacity of 250,000 gallons or more shall consist of the following:
(2) Construction beneath any aboveground piping of containment system which meets the following requirements;
(d) Construction of the containment system must be in accordance with professional engineering practices;
Plans and specifications for the secondary containment system must be submitted for approval by the department at least 30 days before construction of the system.
Aboveground and underground piping from the AST is exempt from these requirements provided that pressure tests are performed every five years to demonstrate the piping's integrity.