All individual or small on-site wastewater treatment systems shall be designed to have a capacity at least equal to the anticipated maximum daily flow. For existing facilities where the average daily flow is measured, the anticipated maximum daily wastewater flow shall be assumed to be 150 percent of the average daily flow as the basis for the design of the system. In other cases, the anticipated maximum daily flow capacity shall be determined according to the type of facility as set forth in Table 2.
Gallons/Person/Day
{*Gallons/Unit/Day}
Boarding Houses (withfoodservice)
50
Hotels and Motels (withoutprivatebaths)
40
Hotels and Motels (withprivatebaths)
50
Luxury Residences and Estates
150
Mobile Home Parks (minimum of 3.5 persons)
75
Mobile Home Parks (perspace)
*250
Motels (withprivatebathsandkitchenettesorlaundry)
60
Multiple Family Dwellings or Apartments
75
Rooming Houses (roomswithbaths)
40
Single Family Dwellings (minimum of 3.5 persons, or
120 gallons per bedroom, whichever is greater)
75
Commercial
Airport (per passenger, without food service)
5
Airport (perpublictoiletroom)
*500
Automobile Service Station (pertoiletroom)
*500
Automobile Service Station (pervehicleserved)
*10
Bars and Cocktail Lounges (perpatron)
2
Bars and Cocktail Lounges (perseat)
*20
Bus Stations (withoutfoodservice)
5
Commercial Employees (except factory, plant, or office)
10
Factories and Plants (exclusiveofindustrialwaste)
35
Laundries, Self Service (perwasher)
*600
Offices (peremployee)
15
Restaurants (kitchenwastesperpatron)
3
Restaurants, on Interstate or Through Highways (perseat)
*180
Restaurants, (perseat)
*35
Restaurants (toiletandkitchenwastesperpatron)
10
Restaurants (withpaperserviceperpatron)
1.5
Shopping Centers (perparkingspace)
2
Stores (perpublictoiletroom)
*500
Theaters, Drive-in (not including food, per car space)
*10
Theaters, Movie, Auditorium Type (not including food,
per seat)
*5
Work or Construction Camps (semipermanent, with flush
toilets)
50
Work or Construction Camps (semipermanent, without
flush toilets)
25
Institutional
Hospitals (perbedspace)
250
Institutional and School Employees
15
Institutions Other Than Hospitals (perbedspace)
125
Nursing or Rest Homes (perbedspace)
100
Schools, Boarding
100
Schools, Day (without cafeteria, gym, or showers)
15
Schools, Day (with cafeteria, but not gym or showers)
20
Schools, Day (with cafeteria, gym, and showers)
25
Recreational, Seasonal, or Other
Assembly or Dance Halls
2
Bowling Alleys (perlane)
*75
Bowling Alleys (with restaurant, per lane)
*100
Cabins, Resort
60
Campgrounds, Developed
30
Camps, Day (nomealsserved)
15
Camps, Luxury Resort
125
Churches (persanctuaryseat)
*5
Churches (with kitchens, per sanctuary seat)
*7
Cottages and Small Dwellings (seasonaloccupancy)
50
Country Clubs, Employees
15
Country Clubs (perguest)
25
Country Clubs (perresidentmember)
100
Interstate Rest Areas
5
Parks, Picnic (toiletwasteonly)
5
Parks, Picnic (with bath houses, showers, and flush
toilets)
15
Parks, Travel Trailer (with individual water and sewer
hook-ups, per space)
*100
Parks, Travel Trailer (without individual water and
sewer hook-ups, per space)
*50
Parks (with central toilet and shower facilities, per space)
*75
Store, Resort
3
Swimming Pools with Bath Houses
10
Visitor Center
5
Source: 12 SDR 2, effective July 18, 1985; 13 SDR 129, 13 SDR 141, effective July 1, 1987; transferred from § 74:03:01:57, July 1, 1996.
General Authority: SDCL 34A-2-93.
Law Implemented: SDCL 34A-2-20.