ARSD 74:36:07:117
74 : 36 : 07 : 117 . Existing municipal solid waste landfill active gas collection system monitoring. The owner or operator of an existing municipal solid waste landfill that seeks to comply with an active gas collection system must install a sampling port and a thermometer, other temperature measuring device, or an access port for temperature measurements at each wellhead. The owner or operator must :
(2) Monitor nitrogen or oxygen concentration in the landfill gas on a monthly basis as follows:
(b) Unless an alternative test method is established, the oxygen level must be determined by an oxygen meter using 40 C.F.R. Part 60, Appendix A, Method 3A or 3C (all July 1, 2024) or ASTM D6522-11, if the sample location is prior to combustion, except that the following apply:
(3) Monitor the temperature of the landfill gas on a monthly basis. The temperature measuring device must be calibrated annually using the procedure in 40 C.F.R. Part 60, Appendix A-1, Method 2, Section 10.3 (July 1, 2024).
Reference: ASTM D62522-11, 2011 edition, American Society of Testing and Materials. Copies may be obtained at https://www.astm.org. Cost $83.
Source: 46 SDR 64, effective November 25, 2019 ; 52 SDR 27, effective September 17, 2025 .
General Authority: SDCL 34A-1-6 , 34A-1-18 .
Law Implemented: SDCL 34A-1-18 .
Prior versions effective: 2019-11-25.