Drawing requirements for aboveground storage.
Effective Sep 11, 199623 SDR 32Source: SL 1975, ch 16, § 1; transferred from § 61:10:03:03, 8 SDR 87, 8 SDR 134, effective July 1, 1982; 12 SDR 151, 12 SDR 155, effective July 1, 1986; 18 SDR 50, effective September 16, 1991; 23 SDR 32, effective September 11, 1996. | General Authority: SDCL 34-29B-2 , 34-38-35. | Law Implemented: SDCL 34-29B-2 , 34-38-24 , 34-38-25 , 34-38-26.
For aboveground storage, the drawings shall show:
- (1) The capacity of each tank;
- (2) The dimensions of each tank;
- (3) The class of liquid to be stored in each tank;
- (4) The type of tank supports;
- (5) The clearances between tanks;
- (6) The type of venting and pressure relief used and the combined capacity of all venting and pressure relief valves on each tank;
- (7) The tank control valves;
- (8) The location and type of pump;
- (9) Electrical schematic;
- (10) Vehicle access;
- (11) Method of storage and dispensing; and
- (12) Distances from tanks and dispensers to property lines and buildings, fire appliances, collision barriers, and emergency controls.