Emergency electrical service shall be furnished to circuits as follows:
- (1) Lighting of exit ways and all necessary ways of approach to them, including exit signs and exit direction signs, exterior of exits, exit doorways, stairways, and corridors;
- (2) Surgical room operating lights;
- (3) Lighting for laboratory, recovery room, staff stations, and medication preparation areas;
- (4) Lighting for the generator set location, the switch gear location, and the boiler room;
- (5) Equipment essential to life safety and for protection of important equipment or vital materials;
- (6) Staff calling system;
- (7) Alarm system, including fire alarms actuated at manual stations;
- (8) Water flow alarm devices of sprinkler system if electrically operated;
- (9) Fire detecting and smoke detecting systems;
- (10) Paging or speaker systems if intended for issuing instructions during emergency conditions;
- (11) Alarms required for nonflammable medical gas systems, if installed;
- (12) Pump for central suction system;
- (13) Sewage or sump lift pump, if installed;
- (14) Receptacles for blood bank refrigerator;
- (15) At least two duplex receptacles for the laboratory;
- (16) Receptacles in operating and recovery rooms except those for X ray;
- (17) Duplex receptacles in patient corridors; and
- (18) Equipment, such as burners and pumps, necessary for operation of one or more boilers required for heating and sterilization and their necessary auxiliaries and controls.