20:44:22 :25. Electrical receptacles in health care facilities. Patient care space in health care facilities, as defined in Article 517 of the National Electrical Code , must have receptacles listed for hospital use in other than hazardous locations. Such receptacles are identified by the marking "Hospital Only" or by the marking "Hospital Grade" and a green dot on the receptacle. The green dot must be visible after installation.