ARSD 20:44:22:24
In new structures, additional working spaces for switchboards, panelboards, and motor control centers operating at 600 volts, nominal, or less, to ground shall extend two feet from the front of the dedicated space and two feet from the top of the working spaces specified in the National Electrical Code. This applies only to items not a part of the electrical installation.
Source: 19 SDR 155, effective April 14, 1993; transferred from § 20:44:05:29, August 12, 1994; 29 SDR 87, effective December 24, 2002 ; 43 SDR 181, effective July 10, 2017.
General Authority: SDCL 36-16-12.
Law Implemented: SDCL 36-16-12.
Prior versions effective: 2002-12-24.