The tier 4 interconnection is considered complete when:
- (1) All interconnection facilities and system upgrades are completed and operational;
- (2) The small generator facility installation is inspected and approved by the electric code inspector with jurisdiction over the interconnection;
- (3) There is a successful completion of the witness test, if conducted by a public utility;
- (4) The parties execute a certificate of completion; and
- (5) The parties execute an interconnection agreement.