For a small generator facility to interconnect to a distribution circuit that is not networked, the following criteria shall be met for a tier 3 interconnection:
- (1) The small generator facility has an electric nameplate capacity of 10 megawatts or less;
- (2) The aggregated total of the electric nameplate capacity of all of the generators on the circuit, including existing FERC wholesale generators, FERC wholesale generators with a higher queue position, and the proposed small generator facility, is 10 megawatts or less;
- (3) The small generator facility does not export power beyond the point of interconnection and employs reverse power relays or other protection functions that prevent power flow onto the EDS;
- (4) The small generator facility's proposed interconnection is to a radial distribution circuit;
- (5) The small generator facility is not served by a shared transformer;
- (6) The interconnection will use only existing public utility facilities and the applicant's proposed facilities; and
- (7) If the public utility's distribution circuit utilizes high speed reclosing with less than 2 seconds of interruption, the proposed generator may not be a synchronous machine.
Source: 35 SDR 305, effective July 1, 2009.
General Authority: SDCL 49-34A-27 , 49-34A-93.
Law Implemented: SDCL 49-34A-27 , 49-34A-93.