S.C. Code Ann. Regs. 71-5500
1. All components, devices, and equipment, structures and other related items for facilities shall be inspected upon initial installation or registration, or at the time of alteration or repair prior to issuing an operating certificate and a minimum of one (1) time per year thereafter, prior to renewing an operating certificate.
Exceptions:
a) All nuclear facilities employing high radiation shall be inspected at least once every two (2) years or before use by workers during routine plant shutdown. Such inspections may be scheduled to coincide with routine plant shutdown.
b) Dumbwaiters shall be inspected each time they are installed or altered.
c) Handicap lifts shall be inspected every five (5) years.
d) Manlifts, television tower elevators and special purpose elevators shall be inspected every seven (7) years.
4. An owner who desires to operate a new elevator facility on a temporary basis pending completion of a project may apply for a temporary operating certificate. A temporary operating certificate, good for sixty (60) days, will be granted where:
C. the facility complies with all requirements of the ANSI A17.1 and SBC and NEC except:
HISTORY: Added by State Register Volume 10, Issue No. 6, dated June 27, 1986, eff July 1, 1986. Amended by State Register Volume 11, Issue No. 6, eff June 26, 1987; State Register Volume 12, Issue No. 5, eff May 27, 1988; State Register Volume 13, Issue No. 5, eff May 26, 1989; State Register Volume 17, Issue No. 5, Part 3, eff May 28, 1993; State Register Volume 28, Issue No. 3, eff March 26, 2004; SCSR 49-5 Doc. No. 5353, eff May 23, 2025.