S.C. Code Ann. Regs. 61-58.5
Table of Contents
Z. Use of Other Non-Centralized Treatment Devices
AA. Treatment Techniques
BB. Approved Laboratories
CC. Alternative Analytical Techniques
DD. and EE. [Deleted]
A. Applicability.
This regulation shall apply to each public water system, unless the water system meets all of the following conditions:
B. Maximum Contaminant Levels for Inorganic Chemicals
(2) The maximum contaminant levels for inorganic chemicals are as follows:
| Contaminant | Level(mg/l) | |
| (a) | Arsenic | 0.010** |
| (b) | Asbestos | 7 Million Fibers/liter |
| (longer than 10/μm) | ||
| (c) | Barium | 2.0 |
| (d) | Cadmium | 0.005 |
| (e) | Chromium | 0.1 |
| (f) | Fluoride | 4.0 |
| (g) | Mercury | 0.002 |
| (h) | Nitrate (as Nitrogen) | 10 |
| (i) | Nitrite (as Nitrogen) | 1 |
| (j) | Total Nitrate and | |
| Nitrite (as Nitrogen) | 10 | |
| (k) | Selenium | 0.05 |
| (l) | Antimony | 0.006 |
| (m) | Beryllium | 0.004 |
| (n) | Cyanide (as free Cyanide) | 0.2 |
| (o) | Thallium | 0.002 |
| **The MCL for arsenic is 0.05 milligrams per liter (mg/l) for all public water systems until January 23, 2006. |
(3) At the discretion of the Department, nitrate levels not to exceed twenty milligrams per liter may be allowed in a non-community water system if the supplier of water demonstrates to the satisfaction of the Department that:
C. Primary Inorganic Chemical Sampling and Analytical Requirements
(2) Analytical methods used to comply with Section B above, shall be made using EPA-approved methods listed in 40 CFR 141. Analyses for the purpose of determining compliance with Section B above are required as follows:
(7) Monitoring for the purpose of determining compliance with the maximum contaminant levels specified in Section B (2) above, shall be conducted as follows:
(d) The Department may reduce the total number of samples which must be analyzed by allowing the use of compositing. Composite samples from a maximum of five samples are allowed, provided that the detection limit of the method used for analysis is less than one-fifth of the MCL. Compositing of samples must be done in the laboratory.
(i) If the concentration in the composite sample is greater than or equal to one-fifth of the MCL of any inorganic chemical, then a follow-up sample must be taken within 14 days at each sampling point included in the composite. These samples must be analyzed for the contaminants which exceeded one-fifth of the MCL in the composite sample. Detection limits for each analytical method and inorganic contaminant shall be in accordance with those listed in 40 CFR 141.
| DETECTION LIMITS FOR INORGANIC CONTAMINANTS | |||
| Contaminant | MCL(mg/l) | Methodology | Detection Limit(mg/l) |
| Antimony | 0.006 | Atomic Absorption; Furnace | 0.003 |
| Atomic Absorption; Platform | 0.00086 | ||
| ICP-Mass Spectrometry | 0.0004 | ||
| Hydride-Atomic Absorption | 0.001 | ||
| Asbestos | 7 MFL2 | Transmission Electron Microscopy | 0.01 MFL |
| Barium | 2 | Atomic Absorption; furnace technique | 0.002 |
| Atomic Absorption; direct aspiration | 0.1 | ||
| Inductively Coupled Plasma | 0.002(0.001)1 | ||
| Beryllium | 0.004 | Atomic Absorption; Furnace | 0.0002 |
| Atomic Absorption; Platform | 0.000026 | ||
| Inductively Coupled Plasma3 | 0.0003 | ||
| ICP-Mass Spectrometry | 0.0003 | ||
| Cadmium | 0.005 | Atomic Absorption; furnace technique | 0.0001 |
| Inductively Coupled Plasma | 0.0011 | ||
| Chromium | 0.1 | Atomic Absorption; furnace technique | 0.001 |
| Inductively Coupled Plasma | 0.007(0.001)1 | ||
| Cyanide | 0.2 | Distillation, Spectrophotometric4 | 0.02 |
| Distillation, Automated, | |||
| Spectrophotometric4 | 0.005 | ||
| Distillation, Selective Electrode4 | 0.05 | ||
| Distillation, Amenable, | |||
| Spectrophotometric5 | 0.02 | ||
| Mercury | 0.002 | Manual Cold Vapor Technique | 0.0002 |
| Automated Cold Vapor Technique | 0.0002 | ||
| Nickel | 0.1 | Atomic Absorption; Furnace | 0.001 |
| Atomic Absorption; Platform | 0.00065 | ||
| Inductively Coupled Plasma3 | 0.005 | ||
| ICP-Mass Spectrometry | 0.0005 | ||
| Nitrate | 10(as N) | Manual Cadmium Reduction | 0.01 |
| Automated Hydrazine Reduction | 0.01 | ||
| Automated Cadmium Reduction | 0.05 | ||
| Ion Selective Electrode | 1 | ||
| Ion Chromatography | 0.01 | ||
| Nitrite | 1(as N) | Spectrophotometric | 0.01 |
| Automated Cadmium Reduction | 0.05 | ||
| Manual Cadmium Reduction | 0.01 | ||
| Ion Chromatography | 0.004 | ||
| Selenium | 0.05 | Atomic Absorption; furnace | 0.002 |
| Atomic Absorption; gaseous hydride | 0.002 | ||
| Thallium | 0.002 | Atomic Absorption; Furnace | 0.001 |
| Atomic Absorption; Platform | 0.00076 | ||
| ICP-Mass Spectrometry | 0.0003 | ||
| 1MFL = million fibers per liter > 10μm. | |||
| 2Using a 2X preconcentration step as noted in method 200.7. Lower MDLs may be achieved when using a 4X preconcentration. | |||
| 3Screening method for total cyanides. | |||
| 4Measures “free” cyanides. | |||
| 5Lower MDLs are reported using stabilized temperature graphite furnace atomic absorption. |
(ii) If the population served by the system is greater than 3,300 persons, then compositing may only be permitted by the Department at sampling points within a single system. In systems serving 3,300 persons or less, the Department may permit compositing among different systems provided the 5-sample limit is maintained.
(iii) If duplicates of the original sample taken from each sampling point used in the composite are available, the system may use these instead of resampling. The duplicates must be analyzed and the results reported to the Department within 14 days of collection.
(8) The frequency of monitoring conducted to determine compliance with the maximum contaminant level for asbestos specified in Section B(2) above shall be conducted as follows:
(c) The Department may grant a waiver based on a consideration of the following factors:
(9) The frequency of monitoring conducted to determine compliance with the maximum contaminant levels in Section B(2) above for antimony, arsenic, barium, beryllium, cadmium, chromium, cyanide, fluoride, mercury, nickel, selenium, and thallium shall be as follows:
(e) In determining the appropriate reduced monitoring frequency, the Department shall consider:
(ii) The degree of variation in reported concentrations; and
(iii) Other factors which may affect contaminant concentrations such as changes in groundwater pumping rates, changes in the system’s configuration, changes in the system’s operating procedures, or changes in stream flows or characteristics.
(10) All public water systems (community; non-transient, non-community; and transient, non-community) shall monitor to determine compliance with the maximum contaminant level for nitrate in Section B above.
(11) All public water systems (community; non-transient, non-community; and transient, non-community systems) shall monitor to determine compliance with the maximum contaminant level for nitrite in Section B above.
(12) Confirmation samples:
(15) Compliance with Section B(2) above (as appropriate) shall be determined based on the analytical result(s) obtained at each sampling point.
(17) Inorganic analysis:
(a) Analysis for antimony, arsenic, barium, beryllium, cadmium, chromium, cyanide, fluoride, mercury, nickel, nitrate, nitrite, selenium, and thallium shall be conducted using EPA-approved methods listed in 40 CFR 141.
| INORGANIC CONTAMINANTS ANALYTICAL METHODS | ||||||
| Reference (Method Number) | ||||||
| Contaminant | Methodology | EPA | ASTM2 | SM3 | USGS4 | Other |
| Antimony | Atomic Absorption; Furnace6 | 204.21 | 3113 | |||
| Atomic Absorption; Platform6 | 200.96 | |||||
| ICP-Mass Spectrometry6 | 200.86 | |||||
| Hydride-Atomic Absorption9 | D-3697-87 | |||||
| Asbestos | Transmission Electron Microscopy | EPA12 | ||||
| Barium | Atomic Absorption; Furnace6 | 208.21 | 3113B | |||
| Atomic Absorption; Direct6 | 208.11 | 3111D | ||||
| Inductively Coupled Plasma6 | 200.76 | 3120 | ||||
| Beryllium | Atomic Absorption; Furnace6 | 210.21 | D-3645-84B | 3113 | ||
| Atomic Absorption; Platform6 | 200.96 | |||||
| Inductively Coupled Plasma6 | 200.76 | 3120 | ||||
| ICP-Mass Spectrometry6 | 200.86 | |||||
| Cadmium | Atomic Absorption; Furnace6 | 213.21 | 3113B | |||
| Inductively Coupled Plasma6 | 200.76 | |||||
| Chromium | Atomic Absorption; Furnace6 | 218.21 | 3113B | |||
| Inductively Coupled Plasma6 | 200.76 | 3120 | ||||
| Cyanide | Distillation, Spec. | 335.21 | D-2036-89A | 4500-CN-D | 1330085 | |
| Distillation, Automated, Spec. | 335.31 | 4500-CN-E | ||||
| Distillation, Selective Electrode | D-2036-89A | 4500-CN-F | ||||
| Distillation, Amenable, Spec. | 335.11 | D-2036-89B | 4500-CN-G | |||
| Mercury | Manual Cold Vapor Technique9 | 245.11 | D3223-86 | 3112B | ||
| Automated Cold Vapor Technique9 | 245.21 | |||||
| Nickel | Atomic Absorption; Furnace6 | 249.21 | 3113 | |||
| Atomic Absorption; Platform6 | 200.96 | |||||
| Atomic Absorption; Direct6 | 249.11 | 3111B | ||||
| Inductively Coupled Plasma6 | 200.76 | 3120 | ||||
| ICP-Mass Spectrometry6 | 200.86 | |||||
| Nitrate | Manual Cadmium Reduction | 353.31 | D3867-90 | 4500-NO3-E | ||
| Automated Hydrazine Reduction | 353.11 | |||||
| Automated Cadmium Reduction | 353.21 | D3867-90 | 4500-NO3-F | |||
| Ion Selective Electrode | WeWWG/ | 58807 | ||||
| Ion Chromatograph | 300.011 | B-10118 | ||||
| Nitrite | Spectrophotometric | 354.11 | ||||
| Automated Cadmium Reduction | 353.21 | D3867-90 | 4500-NO3-F | |||
| Manual Cadmium Reduction | 353.31 | D3867-90 | 4500-NO3-E | |||
| Ion Chromatography | 300.011 | B-10118 | ||||
| Selenium | Hydride-Atomic Absorption9 | D3859-84A | 3114B | |||
| Atomic Absorption; Furnace610 | 270.21 | D3959-88 | 3113B | |||
| Thallium | Atomic Absorption; Furnace6 | 279.21 | 3113 | |||
| Atomic Absorption; Platform6 | 200.95 | |||||
| ICP-Mass Spectrometry6 | 200.85 | |||||
| 1”Methods of Chemical Analysis of Water and Wastes,” EPA Environmental Monitoring Systems Laboratory, Cincinnati, OH 45268 March 1983. EPA-600/4-79-020. | ||||||
| 2Annual Book of ASTM Standards, Vols. 11.01 and 11.02, 1991. American Society of Testing and Materials, 1916 Race Street, Philadelphia, PA 19103. | ||||||
| 3”Standard Methods for the Examination of Water and Wastewater,” 17th edition, American Public Health Association, American Water Works Association. Water Pollution Control Federation, 1989. | ||||||
| 4Techniques of Water Resources Investigations of the U.S. Geological Survey, “Methods for Determination of Inorganic Substances in Water and Fluvial Sediments,” Book 5, Chapter A-1, Third edition, 1989. Available at Superintendent of Documents, U.S. Government Printing Office, Washington, DC 20402. | ||||||
| 5”Methods for Determination of Metals in Environmental Samples.” Available at NTIS, PB 91-231498. | ||||||
| 6Samples that contain less than 1 NTU (nephelometric turbidity unit) and are properly preserved (conc HNO3 to pH < 2) may be analyzed directly (without digestion) for total metals, otherwise, digestion is required. Turbidity must be measured on the preserved samples just prior to initiation of metal analysis. When digestion is required, the total recoverable technique as defined in the method must be used. | ||||||
| 7”Orion Guide to Water and Wastewater Analysis.” For WeWWG/5880, p.5, 1985. Orion Research, Inc., Cambridge, MA. | ||||||
| 8”Waters Test Method for Determination of Nitrite/Nitrate in Water Using Single Column Ion Chromatography, Method B-1011. Millipore Corporation, Waters Chromatography Division, 34 Maple Street, Milford, MA 01757. | ||||||
| 9For the gaseous hydride determinations of antimony and selenium and for the determination of mercury by the cold vapor techniques, the proper digestion technique as defined in the method must be followed to ensure the element is in the proper state for analyses. | ||||||
| 10Add 2 ml of 30% H2O2 and an appropriate concentration of matrix modifier Ni(NO2) + 6H2O (nickel nitrate) to samples. | ||||||
| 11”Method 300. Determination of Inorganic Anions in Water by Ion Chromatography.” Inorganic Chemistry Branch, Environmental Monitoring Systems Laboratory. August 1991. | ||||||
| 12”Analytical Method for Determination of Asbestos Fibers in Water,” EPA-600/4-83-043, September 1983, U.S. EPA Environmental Research Laboratory, Athens, GA 30613. |
D. Maximum Contaminant Levels for Organic Chemicals
(2) The maximum contaminant levels for organic chemicals are as follows:
| Contaminant | Level, mg/l | ||||
| (a) | Reserved | ||||
| (b) | (i) | Alachlor | 0.002 | ||
| (ii) | Atrazine | 0.003 | |||
| (iii) | Carbofuran | 0.04 | |||
| (iv) | Chlordane | 0.002 | |||
| (v) | Dibromochloropropane | 0.0002 | |||
| (vi) | 2,4-D | 0.07 | |||
| (vii) | Ethylene dibromide (EDB) | 0.00005 | |||
| (viii) | Heptachlor | 0.0004 | |||
| (ix) | Heptachlor epoxide | 0.0002 | |||
| (x) | Lindane | 0.0002 | |||
| (xi) | Methoxychlor | 0.04 | |||
| (xii) | Polychlorinated biphenyls(PCBs) | 0.0005 | |||
| (xiii) | Pentachlorophenol | 0.001 | |||
| (xiv) | Toxaphene | 0.003 | |||
| (xv) | 2,4,5-TP | 0.05 | |||
| (xvi) | Benzo[a]pyrene | 0.0002 | |||
| (xvii) | Dalapon | 0.2 | |||
| (xviii) | Di(2-ethylhexyl)adipate | 0.4 | |||
| (xvix) | Di(2-ethylhexyl)phthalate | 0.006 | |||
| (xx) | Dinoseb | 0.007 | |||
| (xxi) | Diquat | 0.02 | |||
| (xxii) | Endothall | 0.1 | |||
| (xxiii) | Endrin | 0.002 | |||
| (xxiv) | Glyphosate | 0.7 | |||
| (xxv) | Hexachlorobenzene | 0.001 | |||
| (xxvi) | Hexachlorocyclopentadiene | 0.05 | |||
| (xxvii) | Oxamyl (vydate) | 0.2 | |||
| (xxviii) | Picloram | 0.5 | |||
| (xxvix) | Simazine | 0.004 | |||
| (xxx) | 2,3,7,8-TCDD (Dioxin) | 3 X 10-8 |
E. Organic Chemicals Other Than Total Trihalomethanes, Sampling and Analytical Requirements
(7) Analytical methods used to comply with Section D(2)(b) above, shall be made using EPA-approved methods listed in 40 CFR 141. Analysis of the contaminants listed in Section D(2)(b) above, for the purposes of determining compliance with the maximum contaminant level shall be conducted as follows:
(d) Monitoring frequency:
(ii) Systems serving more than 3,300 persons which do not detect a contaminant in the initial compliance period, may reduce the sampling frequency to a minimum of two quarterly samples in one year during each repeat compliance period.
(iii) Systems serving 3,300 persons or less which do not detect a contaminant in the initial compliance period may reduce the sampling frequency to a minimum of one sample during each repeat compliance period.
(f) The Department may grant a waiver after evaluating the following factor(s): Knowledge of previous use (including transport, storage, or disposal) of the contaminant within the watershed or zone of influence of the system. If a determination by the Department reveals no previous use of the contaminant within the watershed or zone of influence, a waiver may be granted. If previous use of the contaminant is unknown or it has been used previously, then the following factors shall be used to determine whether a waiver is granted.
(ii) The proximity of the system to a potential point or non-point source of contamination. Point sources include spills and leaks of chemicals at or near a water treatment facility or at manufacturing, distribution, or storage facilities, or from hazardous and municipal waste landfills and other waste handling or treatment facilities. Non-point sources include the use of pesticides to control insect and weed pests on agricultural areas, forest lands, home and gardens, and other land application uses.
(iii) The environmental persistence and transport of the pesticide or PCBs.
(g) If an organic contaminant listed in Section D(2)(b) above, is detected (as defined by paragraph (7)(r) of this section) in any sample, then:
(ii) The Department may decrease the quarterly monitoring requirement specified in paragraph (7)(g)(i) of this section provided it has determined that the system is reliably and consistently below the maximum contaminant level. In no case shall the Department make this determination unless a groundwater system takes a minimum of two quarterly samples and a surface water system takes a minimum of four quarterly samples.
(iii) After the Department determines the system is reliably and consistently below the maximum contaminant level the Department may allow the system to monitor annually. Systems which monitor annually must monitor during the quarter that previously yielded the highest analytical result.
(j) The Department may reduce the total number of samples a system must analyze by allowing the use of compositing. Composite samples from a maximum of five sampling points are allowed, provided that the detection limit of the method used for analysis is less than one-fifth of the MCL. Compositing of samples must be done in the laboratory and analyzed within 14 days of sample collection.
(ii) If duplicates of the original sample taken from each sampling point used in the composite are available, the system may use these duplicates instead of resampling. The duplicate must be analyzed and the results reported to the Department within 14 days of collection.
(iii) If the population served by the system is more than 3,300 persons, then compositing may only be permitted by the Department at sampling points within a single system. In systems serving 3,300 persons or less, the Department may permit compositing among different systems provided the 5-sample limit is maintained.
(k) Compliance with Section D(2)(b) above, shall be determined based on the analytical results obtained at each sampling point. If one sampling point is in violation of an MCL, the system is in violation of the MCL.
(ii) Systems monitoring annually or less frequently whose sample result exceeds the regulatory detection level as defined by paragraph (7)(r) of this section must begin quarterly sampling. The system will not be considered in violation of the MCL until it has completed one year of quarterly sampling.
(iii) If any sample result will cause the running annual average to exceed the MCL at any sampling point, the system is out of compliance with the MCL immediately.
(m) Analysis for PCBs shall be conducted using EPA-approved methods listed in 40 CFR 141.
(ii) [Reserved]
(iii) Compliance with the PCB MCL shall be determined based upon the quantitative results of analyses using EPA-approved methods listed in 40 CFR 141.
(r) Detection as used in this paragraph shall be defined as greater than or equal to the following concentrations for each contaminant.
| Contaminant | Detection Limit | |||
| Atrazine | 0.0001 mg/l | |||
| Benzo[a]pyrene | 0.00002 mg/l | |||
| Carbofuran | 0.0009 mg/l | |||
| Chlordane | 0.0002 mg/l | |||
| Dalapon | 0.001 mg/l | |||
| Dibromochloropropane (DBCP) | 0.00002 mg/l | |||
| Di (2-ethylhexly) adipate | 0.0006 mg/l | |||
| Di (2-ethylhexly) phthalate | 0.0006 mg/l | |||
| Dinoseb | 0.0002 mg/l | |||
| Diquat | 0.0004 mg/l | |||
| 2,4-D | 0.0001 mg/l | |||
| Endothall | 0.009 mg/l | |||
| Endrin | 0.00001 mg/l | |||
| Ethylene dibromide (EDB) | 0.00001 mg/l | |||
| Glyphosate | 0.006 mg/l | |||
| Heptachlor | 0.00004 mg/l | |||
| Heptachlor epoxide | 0.00002 mg/l | |||
| Hexachlorobenzene | 0.0001 mg/l | |||
| Hexachlorocyclopentadiene | 0.0001 mg/l | |||
| Lindane | 0.00002 mg/l | |||
| Methoxychlor | 0.0001 mg/l | |||
| Oxamyl | 0.002 mg/l | |||
| Picloram | 0.0001 mg/l | |||
| Polychlorinated biphenyls (PCBs) (as decachlorobiphenyl) | 0.0001 mg/l | |||
| Pentachlorophenol | 0.00004 mg/l | |||
| Simazine | 0.00007 mg/l | |||
| Toxaphene | 0.001 mg/l | |||
| 2,3,7,8-TCDD (Dioxin) | 0.000000005 mg/l | |||
| 2,4,5-TP (Silvex) | 0.0002 mg/l |
F. Maximum Contaminant Levels (MCLs) for Microbiological Contaminants.
(1) Until March 31, 2016, the total coliform MCL is based on the presence or absence of total coliforms in a sample, rather than coliform density.
(3) Beginning April 1, 2016, a system is in compliance with the MCL for E. coli for samples taken under provisions of R.61-58.17 unless any of the conditions identified in R.61-58.5.F(3)(a) through (d) occur. For purposes of the public notification requirements in R.61-58.6.E, violation of the MCL may pose an acute risk to health.
(5) The United States Environmental Protection Agency Administrator, pursuant to section 1412 of the federal Safe Drinking Water Act, has identified the following as the best technology, treatment techniques, or other means available for achieving compliance with the maximum contaminant level for total coliforms in R.61-58.5.F (1)and (2) and for achieving compliance with the maximum contaminant level for E. coli in R.61-58.5.F(3):
These maximum contaminant levels shall apply to all public water systems.
G. Microbiological Contaminant Sampling and Analytical Requirements.
(1) Routine Monitoring.
(b) The monitoring frequency for total coliforms for community water systems is based on the population served by the system, as follows:
| Population Served | Minimum # of Samples Per Month | ||
| 25 | to | 1,0001 | 1 |
| 1,001 | to | 2,500 | 2 |
| 2,501 | to | 3,300 | 3 |
| 3,301 | to | 4,100 | 4 |
| 4,101 | to | 4,900 | 5 |
| 4,901 | to | 5,800 | 6 |
| 5,801 | to | 6,700 | 7 |
| 6,701 | to | 7,600 | 8 |
| 7,601 | to | 8,500 | 9 |
| 8,501 | to | 12,900 | 10 |
| 12,901 | to | 17,200 | 15 |
| 17,201 | to | 21,500 | 20 |
| 21,501 | to | 25,000 | 25 |
| 25,001 | to | 33,000 | 30 |
| 33,001 | to | 41,000 | 40 |
| 41,001 | to | 50,000 | 50 |
| 50,001 | to | 59,000 | 60 |
| 59,001 | to | 70,000 | 70 |
| 70,001 | to | 83,000 | 80 |
| 83,001 | to | 96,000 | 90 |
| 96,001 | to | 130,000 | 100 |
| 130,001 | to | 220,000 | 120 |
| 220,001 | to | 320,000 | 150 |
| 320,001 | to | 450,000 | 180 |
| 450,001 | to | 600,000 | 210 |
| 600,001 | to | 780,000 | 240 |
| 780,001 | to | 970,000 | 270 |
| 970,001 | to | 1,230,000 | 300 |
| 1,230,001 | to | 1,520,000 | 330 |
| 1,520,001 | to | 1,850,000 | 360 |
| 1,850,001 | to | 2,270,000 | 390 |
| 2,270,001 | to | 3,020,000 | 420 |
| 3,020,001 | to | 3,960,000 | 450 |
| 3,960,001 | or more | 480 | |
| 1Includes public water systems which have at least fifteen (15) service connections, but serve fewer than twenty-five (25) persons. |
If a community water system serving twenty-five (25) to one-thousand (1,000) persons has no history of total coliform contamination in its current configuration and a sanitary survey conducted in the past five years shows that the system is supplied solely by a protected groundwater source and is free of sanitary defects, the Department may reduce the monitoring frequency specified above, except that in no case may the Department reduce the monitoring frequency to less than one sample per quarter. The Department must approve the reduced monitoring frequency in writing.
(c) The monitoring frequency for total coliforms for non-community water systems is as follows:
(ii) A non-community water system using only ground water (except ground water under the direct influence of surface water) and serving more than one-thousand (1,000) persons during any month shall monitor at the same frequency as a like-sized community water system, as specified in paragraph (1)(b) of this section, except that the Department may reduce this monitoring frequency, in writing, for any month the system serves one-thousand (1,000) persons or fewer. The Department cannot reduce the monitoring frequency to less than once per year. For systems using ground water under the direct influence of surface water, paragraph (1)(c)(iv) of this section applies.
(iii) A non-community water system using surface water, in total or in part, shall monitor at the same frequency as a like-sized community water system, as specified in paragraph (1)(b) of this section, regardless of the number of persons it serves.
(2) Repeat Monitoring.
(e) If a system collecting fewer than five routine samples per month has one or more total coliform-positive samples and the Department does not invalidate the sample(s) under paragraph (3) of this section, it shall collect at least five routine samples during the next month the system provides water to the public, except that the Department may waive this requirement if the conditions of paragraph (2)(e)(i) or (ii) of this section are met. The Department cannot waive the requirement for a system to collect repeat samples in paragraphs (2)(a) through (d) of this section.
(3) Invalidation of total coliform samples.
(a) The Department may invalidate a total coliform-positive sample only if the conditions of paragraph (3)(a)(i), (ii) or (iii) of this section are met.
(ii) The Department, on the basis of the results of repeat samples collected as required by paragraphs (2)(a) through (d) of this section, determines that the total coliform-positive sample resulted from a domestic or other non-distribution system plumbing problem. The Department cannot invalidate a sample on the basis of repeat sample results unless all repeat sample(s) collected at the same tap as the original total coliform-positive sample are also total coliform-positive, and all repeat samples collected within five service connections of the original tap are total coliform-negative (e.g., the Department cannot invalidate a total coliform-positive sample on the basis of repeat samples if all the repeat samples are total coliform-negative, or if the public water system has only one service connection).
(iii) The Department has substantial grounds to believe that a total coliform-positive result is due to a circumstance or condition which does not reflect water quality in the distribution system. In this case, the system shall still collect all repeat samples required under paragraphs (2)(a) through (d) of this section, and use them to determine compliance with the MCL for total coliforms in Section F above. To invalidate a total coliform-positive sample under this paragraph, the decision with the rationale for the decision shall be documented in writing, and approved and signed by the supervisor of the Department official who recommended the decision. The Department shall make this document available to the EPA and the public. The written documentation shall state the specific cause of the total coliform-positive sample, and what action the system has taken, or will take, to correct this problem. The Department may not invalidate a total coliform-positive sample solely on the grounds that all repeat samples are total coliform-negative.
A total coliform-positive sample invalidated under this paragraph does not count towards meeting the minimum monitoring requirements of this section.
(4) Sanitary Surveys.
(a)(i) Public water systems which do not collect five (5) or more routine samples per month shall undergo an initial sanitary survey by June 29, 1994, for community water systems and June 29, 1999, for non-community water systems. hereafter, systems shall undergo another sanitary survey every five (5) years, except that non-community water systems using only protected and disinfected ground water, as defined by the Department, shall undergo subsequent sanitary surveys at least every ten (10) years after the initial sanitary survey. The Department shall review the results of each sanitary survey to determine whether the existing monitoring frequency is adequate and what additional measures, if any, the system needs to undertake to improve drinking water quality.
(5) Fecal coliforms/Escherichia coli (E. coli) testing.
(6) Analytical methodology.
(7) Response to violation.
These sampling and analytical requirements shall apply to community and non-community water systems. Analytical methods used to comply with Section F above, shall be made using EPA-approved methods listed in 40 CFR 141.
H. Maximum Contaminant Levels for Radionuclides.
(4) MCL for beta particle and photon radioactivity.
(b) Except for the radionuclides listed in Table A, the concentration of man-made radionuclides causing 4 mrem total body or organ dose equivalents must be calculated on the basis of two (2) liters per day drinking water intake using the 168 hour data list in “Maximum Permissible Body Burdens and Maximum Permissible Concentrations of Radionuclides in Air and in Water for Occupational Exposure,” NBS (National Bureau of Standards) Handbook 69 as amended August 1963, U.S. Department of Commerce. This incorporation by reference was approved by the Director of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Copies of this document are available from the National Technical Information Service, NTIS ADA 280 282, U.S. Department of Commerce, 5285 Port Royal Road, Springfield, Virginia 22161. The toll-free number is 800-553-6847. Copies may be inspected at EPA’s Drinking Water Docket, 401 M Street, SW, Washington, DC 20460; or at the Office of the Federal Register, 800 North Capitol Street, NW, Suite 700, Washington, DC. If two or more radionuclides are present, the sum of their annual dose equivalent to the total body or to any organ shall not exceed 4 mrem/year.
| TABLE A: AVERAGE ANNUAL CONCENTRATIONS ASSUMED TO PRODUCE A TOTAL BODY OR ORGAN DOSE OF 4 MREM/YR | ||
| Radionuclide | Critical organ | pCi per liter |
| 1. Tritium | Total body | 20,000 |
| 2. Strontium-90 | Bone Marrow | 8 |
(7) Best available technologies (BATs) for radionuclides. The Administrator, pursuant to section 1412 of the Federal Safe Drinking Water Act, hereby identifies as indicated in the following table the best technology available for achieving compliance with the maximum contaminant levels for combined radium-226 and -228, uranium, gross alpha particle activity, and beta particle and photon radioactivity.
| TABLE B: BAT FOR COMBINED RADIUM-226 AND RADIUM-228, URANIUM, GROSS ALPHA PARTICLE ACTIVITY, AND BETA PARTICLE AND PHOTON RADIOACTIVITY | ||
| CONTAMINANT | BAT | |
| 1. | Combined radium-226 and radium-228 | Ion exchange, reverse osmosis, lime softening. |
| 2. | Uranium | Ion exchange, reverse osmosis, lime softening, coagulation/filtration. |
| 3. | Gross alpha particle activity (excluding Radon and Uranium) | Reverse osmosis. |
| 4. | Beta particle and photon radioactivity | Ion exchange, reverse osmosis. |
(8) Small systems compliance technologies list for radionuclides.
| TABLE D: COMPLIANCE TECHNOLOGIES BY SYSTEM SIZE CATEGORY FOR RADIONUCLIDES | ||||
| Contaminant | Compliance technologies1 for system size categories (population served) | |||
| 25—500 | 501—3,300 | 3,300—10,000 | ||
| 1. | Combined radium-226 and radium-228 | 1, 2, 3, 4, 5, 6, 7, 8, 9 | 1, 2, 3, 4, 5, 6, 7, 8, 9 | 1, 2, 3, 4, 5, 6, 7, 8, 9 |
| 2. | Gross alpha particle activity | 3, 4 | 3, 4 | 3, 4 |
| 3. | Beta particle activity and photon activity | 1, 2, 3, 4 | 1, 2, 3, 4 | 1, 2, 3, 4 |
| 4. | Uranium | 1, 2, 4, 10, 11 | 1, 2, 3, 4, 5, 10, 11 | 1, 2, 3, 4, 5, 10, 11 |
| 1Numbers correspond to those technologies found listed in the Table C above. |
I. Monitoring Frequency and Compliance Requirements for Radionuclides in Community Water Systems.
(2) The monitoring and compliance requirements for gross alpha particle activity. radium-226, radium-228, and uranium.
(a) Community water systems (CWSs) must conduct initial monitoring to determine compliance with Section H(2), (3) and (5) above by December 31, 2007. For the purposes of monitoring for gross alpha particle activity, radium-226, radium-228, uranium, and beta particle and photon radioactivity in drinking water, “detection limit” is defined as in Section K(3) below.
(b) Initial monitoring: Systems must conduct initial monitoring for gross alpha particle activity, radium-226, radium-228, and uranium as follows:
(ii) Grandfathering of data: The Department may allow historical monitoring data collected at a sampling point to satisfy the initial monitoring requirements for that sampling point, for the following situations.
(C) To satisfy initial monitoring requirements, a community water system with appropriate historical data for a representative point in the distribution system may use the monitoring data from the last compliance monitoring period that began between June 2000 and December 8, 2003, provided that the Department finds that the historical data satisfactorily demonstrate that each entry point to the distribution system is expected to be in compliance based upon the historical data and reasonable assumptions about the variability of contaminant levels between entry points. The Department must make a written finding indicating how the data conforms to these requirements.
(iii) For gross alpha particle activity, uranium, radium-226, and radium-228 monitoring, the Department may waive the final two quarters of initial monitoring for a sampling point if the results of the samples from the previous two (2) quarters are below the detection limit.
(c) Reduced monitoring: The Department may allow community water systems to reduce the future frequency of monitoring from once every three (3) years to once every six (6) or nine (9) years at each sampling point, based on the following criteria.
(ii) For gross alpha particle activity and uranium, if the average of the initial monitoring results for each contaminant is at or above the detection limit but at or below one-half (1/2) the MCL, the system must collect and analyze for that contaminant using at least one (1) sample at that sampling point every six (6) years. For combined radium-226 and radium-228, the analytical results must be combined. If the average of the combined initial monitoring results for radium-226 and radium-228 is at or above the detection limit but at or below one-half (1/2) the MCL, the system must collect and analyze for that contaminant using at least one (1) sample at that sampling point every six (6) years.
(iii) For gross alpha particle activity and uranium, if the average of the initial monitoring results for each contaminant is above one-half (1/2) the MCL but at or below the MCL, the system must collect and analyze at least one (1) sample at that sampling point every three (3) years. For combined radium-226 and radium-228, the analytical results must be combined. If the average of the combined initial monitoring results for radium-226 and radium-228 is above one-half (1/2) the MCL but at or below the MCL, the system must collect and analyze at least one (1) sample at that sampling point every three (3) years.
(e) A gross alpha particle activity measurement may be substituted for the required radium-226 measurement provided that the measured gross alpha particle activity does not exceed 5 pCi/l. A gross alpha particle activity measurement may be substituted for the required uranium measurement provided that the measured gross alpha particle activity does not exceed 15 pCi/l.
The gross alpha measurement shall have a confidence interval of 95 percent (1.65 sigma, where sigma is the standard deviation of the net counting rate of the sample) for radium-226 and uranium. When a system uses a gross alpha particle activity measurement in lieu of a radium-226 and/or uranium measurement, the gross alpha particle activity analytical result will be used to determine the future monitoring frequency for radium-226 and/or uranium. If the gross alpha particle activity result is less than detection, one-half (1/2) the detection limit will be used to determine compliance and the future monitoring frequency.
(3) Monitoring and compliance requirements for beta particle and photon radioactivity.
(a) Community water systems (both surface and ground water) designated by the Department as vulnerable must sample for beta particle and photon radioactivity. Systems must collect quarterly samples for beta emitters and annual samples for tritium and strontium-90 at each entry point to the distribution system (hereafter called a sampling point), beginning within one quarter after being notified by the Department. Systems already designated by the Department must continue to sample until the Department reviews and either reaffirms or removes the designation.
(b) Community water systems (both surface and ground water) designated by the Department as utilizing waters contaminated by effluents from nuclear facilities must sample for beta particle and photon radioactivity. Systems must collect quarterly samples for beta emitters and iodine-131 and annual samples for tritium and strontium-90 at each entry point to the distribution system (hereafter called a sampling point), beginning within one quarter after being notified by the Department. Systems already designated by the Department as systems using waters contaminated by effluents from nuclear facilities must continue to sample until the Department reviews and either reaffirms or removes the designation.
(ii) For iodine-131, a composite of five consecutive daily samples shall be analyzed once each quarter. As ordered by the Department, more frequent monitoring shall be conducted when iodine-131 is identified in the finished water.
(iii) Annual monitoring for strontium-90 and tritium shall be conducted by means of the analysis of a composite of four consecutive quarterly samples or analysis of four quarterly samples. The latter procedure is recommended.
To determine compliance with the maximum contaminant levels in Section H(4) above for beta particle and photon radioactivity, a system must monitor at a frequency as follows:
(4) General monitoring and compliance requirements for radionuclides.
(c) Compliance: Compliance with Section H(2) through (5) above, will be determined based on the analytical result(s) obtained at each sampling point. If one (1) sampling point is in violation of an MCL, the system is in violation of the MCL.
(ii) For systems monitoring more than once per year, if any sample result will cause the running average to exceed the MCL at any sample point, the system is out of compliance with the MCL immediately.
(iii) Systems must include all samples taken and analyzed under the provisions of this section in determining compliance, even if that number is greater than the minimum required.
J. Maximum Contaminant Level Goals for Radionuclides.
MCLGs for radionuclides are as indicated in the following table:
| Contaminant | MCLG | |
| 1. | Combined radium-226 and radium-228 | Zero. |
| 2. | Gross alpha particle activity (excluding radon and uranium) | Zero. |
| 3. | Beta particle and photon radioactivity | Zero. |
| 4. | Uranium | Zero. |
K. Analytical Methods for Radionuclides.
(3) To judge compliance with the maximum contaminant levels listed in Sections H and J above, averages of data shall be used and shall be round to the same number of significant figures as the maximum contaminant level for the substance in question.
(a) To determine compliance with Section H(2), (3), and (5) above, the detection limit shall not exceed the concentrations in Table B to this paragraph.
| TABLE B: DETECTION LIMITS FOR GROSS ALPHA PARTICLE ACTIVITY, RADIUM 226, RADIUM 228, AND URANIUM | |
| Contaminant | Detection limit |
| Gross alpha particle activity | 3 pCi/L. |
| Radium 226 | 1 pCi/L. |
| Radium 228 | 1 pCi/L. |
| Uranium | 1 microgram/L |
(b) To determine compliance with Section H(4) above, the detection limits shall not exceed the concentrations listed in Table C to this paragraph.
| TABLE C: DETECTION LIMITS FOR MAN-MADE BETA PARTICLES AND PHOTON EMITTERS | |
| Contaminant | Detection limit |
| Tritium | 1,000 pCi/l |
| Strontium-89 | 10 pCi/l |
| Strontium - 90 | 2 pCi/l |
| Iodine-131 | 1 pCi/l |
| Cesium-134 | 10 pCi/l |
| Gross Beta | 4 pCi/l |
| Other radionuclides | 1/10 of the applicable limit |
N. Maximum Contaminant Levels for Volatile Synthetic Organic Chemicals (VOCs).
(2) The maximum contaminant levels for volatile synthetic organic chemicals (VOCs) are as follows:
| Contaminant | MCL (mg/l) | |
| (a) | Vinyl chloride | 0.002 |
| (b) | Benzene | 0.005 |
| (c) | Carbon tetrachloride | 0.005 |
| (d) | 1,2-Dichloroethane | 0.005 |
| (e) | Trichloroethylene | 0.005 |
| (f) | para-Dichlorobenzene | 0.075 |
| (g) | 1,1,-Dichloroethylene | 0.007 |
| (h) | 1,1,1-Trichloroethane | 0.2 |
| (i) | cis-1,2-Dichloroethylene | 0.07 |
| (j) | 1,2-Dichloropropane | 0.005 |
| (k) | Ethylbenzene | 0.7 |
| (l) | Monochlorobenzene | 0.1 |
| (m) | o-Dichlorobenzene | 0.6 |
| (n) | Styrene | 0.1 |
| (o) | Tetrachloroethylene | 0.005 |
| (p) | Toluene | 1 |
| (q) | trans-1,2-Dichloroethylene | 0.1 |
| (r) | Xylenes (total) | 10 |
| (s) | Dichloromethane | 0.005 |
| (t) | 1,2,4-Trichlorobenzene | 0.07 |
| (u) | 1,1,2-Trichloroethane | 0.005 |
O. VOC Monitoring, Sampling and Analytical Requirements
(2) Beginning with the initial compliance period analysis of the contaminants listed in Section N(2) above, for the purpose of determining compliance with the maximum contaminant level shall be conducted as follows:
(h) The Department may grant a waiver after evaluating the following factor(s):
(ii) If previous use of the contaminant is unknown or it has been used previously, then the following factors shall be used to determine whether a waiver is granted.
(n) The Department may reduce the total number of samples a system must analyze by allowing the use of compositing. Composite samples from a maximum of five sampling points are allowed, provided that the detection limit of the method used for analysis is less than one-fifth of the MCL. Compositing of samples must be done in the laboratory and analyzed within fourteen (14) days of sample collection.
(ii) If duplicates of the original sample taken from each sampling point used in the composite are available, the system may use these instead of resampling. The duplicate must be analyzed and the results reported to the Department within fourteen (14) days of collection.
(iii) If the population served by the system is greater than 3,300 persons, then compositing may only be permitted by the State at sampling points within a single system. In systems serving 3,300 persons, the Department may permit compositing among different systems provided the 5-sample limit is maintained.
(iv) Compositing samples prior to GC analysis.
(v) Compositing samples prior to GC/MS analysis.
(o) Compliance with Section N(2) above, shall be determined based on the analytical results obtained at each sampling point. If one sampling point is in violation of an MCL, the system is in violation of the MCL.
(ii) Systems monitoring annually or less frequently whose sample result exceeds the MCL must begin quarterly sampling. The system will not be considered in violation of the MCL until it has completed one year of quarterly sampling.
(iii) If any sample result will cause the running annual average to exceed the MCL at any sampling point, the system is out of compliance with the MCL immediately.
P. Maximum Contaminant Levels for Disinfection Byproducts.
(1) Bromate and Chlorite
(a) Compliance Dates.
Community water systems and non-transient non-community water systems that use a surface water source or a ground water source under the influence of surface water serving 10,000 or more persons must comply with this section beginning January 1, 2002. Community water systems and non-community non-transient water systems that use a surface water source or a ground water source under the influence of surface water serving fewer than 10,000 persons and community water systems and non-community non-transient water systems using only ground water not under the direct influence of surface water must comply with this section beginning January 1, 2004.
The maximum contaminant levels (MCLs) for bromate and chlorite are as follows:
| Disinfection Byproduct | MCL (mg/L) |
| Bromate | 0.010 |
| Chlorite | 1.0 |
(2) TTHM and HAA5.
(a) Stage 1 DBP Rule Running Annual Average (RAA) compliance.
The maximum contaminant levels (MCLs) for TTHM and HAA5 are as follows:
| Disinfection Byproduct | MCL (mg/L) |
| Total Trihalomethanes (TTHM) | 0.080 |
| Haloacetic Acids (five) (HAA5) | 0.060 |
(b) Stage 2 DBP Rule Locational Running Annual Average (LRAA) compliance.
The maximum contaminant levels (MCLs) for TTHM and HAA5 are as follows:
| Disinfection Byproduct | MCL (mg/L) |
| Total Trihalomethanes (TTHM) | 0.080 |
| Haloacetic Acids (five) (HAA5) | 0.060 |
Q. Maximum Residual Disinfectant Levels (MRDLs) for Disinfectants.
(1) Maximum residual disinfectant levels (MRDLs) are as follows:
| Disinfectant Residual | MRDL (mg/L) |
| Chlorine | 4.0 (as Cl2) |
| Chloramines | 4.0 (as Cl2) |
| Chlorine dioxide | 0.8 (as ClO2) |
(2) Compliance dates.
R. Secondary Maximum Contaminant Levels.
(2) The secondary maximum contaminant levels are as follows:
| Contaminant | Level |
| Aluminum | 0.05 to 0.2 mg/l |
| Chloride | 250 mg/l |
| Color | 15 color units |
| Copper | 1 mg/l |
| Corrosivity | Noncorrosive |
| Fluoride | 2.0 mg/l |
| Foaming agents | 0.5 mg/l |
| Iron | 0.3 mg/l |
| Manganese | 0.05 m/gl |
| Odor | 3 threshold odor number |
| pH | 6.5 to 8.5 s.u. |
| Silver | 0.1 mg/l |
| Sulfate | 250 mg/l |
| Total Dissolved Solids (TDS) | 500 mg/l |
| Zinc | 5 mg/l |
S. Secondary Maximum Contaminant Levels Sampling and Analytical Requirements.
T. Special Monitoring for Inorganic and Organic Contaminants.
(1) All community and non-transient non-community water supply systems shall conduct special monitoring for the following contaminants. Systems serving 10,000 or fewer persons are not required to monitor for the contaminants in the section after December 31, 1998.
| Chloroform | 1,3-Dichloropropane |
| Bromodichloromethane | Chloromethane |
| Chlorodibromomethane | Bromomethane |
| Bromoform | 1,2,3-Trichloropropane |
| Chlorobenzene | 1,1,1,2-Tetrachloroethane |
| m-Dichlorobenzene | Chloroethane |
| 2,2-Dichloropropane | 1,1-Dichloropropene |
| o-Chlorotoluene | 1,1-Dichloroethane |
| Bromobenzene | 1,1,2,2-Tetrachloroethane |
| 1,3-Dichloropropene | p-Chlorotoluene |
(2) Monitoring for the organic compounds listed in paragraph (1) of this section, shall begin no later than the date specified below:
| Population Served | Initial Monitoring Date |
| >10,000 | No later than January 1, 1988 |
| 3,300-10,000 | No later than January 1, 1989 |
| <3,300 | No later than January 1, 1991 |
(10) At the Department’s discretion, community water systems and non-transient non-community water systems may be required to conduct special monitoring for the following contaminants:
| 1,2,4-Trimethylbenzene | p-Isopropyltoluene |
| 1,2,4-Trichlorobenzene | Isopropylbenzene |
| 1,2,3-Trichlorobenzene | Tert-butylbenzene |
| n-Propylbenzene | Sec-butylbenzene |
| n-Butylbenzene | Fluorotrichloromethane |
| Naphthalene | Dichlorodifluoromethane |
| Hexachlorobutadiene | Bromochloromethane |
| 1,3,5-Trimethylbenzene |
(13) Monitoring of the contaminants listed in paragraphs (13)(k) and (l) of this section, shall be conducted as follows:
(k) List of Unregulated Organic Contaminants:
| Organic Contaminants | EPA Analytical Method |
| Aldicarb | 531.1 |
| Aldicarb sulfone | 531.1 |
| Aldicarb sulfoxide | 531.1 |
| Aldrin | 505, 508, 525.1 |
| Butachlor | 507, 525.1 |
| Carbaryl | 531.1 |
| Dicamba | 515.1 |
| Dieldrin | 505, 508, 525.1 |
| 3-Hydroxycarbofuran | 531.1 |
| Methomyl | 531.1 |
| Metolachlor | 507, 525.1 |
| Metribuzin | 507, 525.1 |
| Propachlor | 508, 525.1 |
(l) List of Unregulated Inorganic Contaminants:
| Inorganic Contaminant | EPA Analytical Method |
| Sulfate | Colorimetric |
U. Special Monitoring for Sodium.
V. Special Monitoring for Corrosivity Characteristics.
(4) The supplier of water for applicable community water systems shall identify and report to the Department whether the following construction materials are present in their distribution system:
(1)-(3) [Reserved]
W. Special Monitoring and Notification Requirements.
The Department shall perform such monitoring as is necessary to insure the quality and integrity of results of tests, measurements, or analyses reported by the supplier of water. Should such monitoring by the Department indicate a violation of the maximum contaminant levels, or the presence of any contaminant at levels considered to be a real or potential threat to the public’s health, the Department at its discretion may notify the public or require the supplier of water to notify the public pursuant to R.61-58.6.E, or other method deemed appropriate by the Department and initiate the necessary action to eliminate the violation or contaminant.
X. Monitoring of Consecutive Public Water Systems.
When a public water system supplies water to one or more other public water systems, the Department may modify the monitoring requirements imposed by this regulation to the extent that the interconnection of the systems justifies treating them as a single system for monitoring purposes. Any modified monitoring shall be conducted pursuant to a schedule specified by the Department and concurred in by the Administrator.
Y. Criteria and Procedures for Public Water Systems using Point-of-Entry Devices.
(4) The public water system must properly apply effective technology under a plan approved by the Department and must maintain the microbiological safety of the water.
Z. Use of Other Non-Centralized Treatment Devices.
(2) Treatment techniques for acrylamide and epichlorohydrin. Each public water system must certify annually in writing to the Department (using third party or manufacturer’s certification) that when acrylamide and epichlorohydrin are used in drinking water systems, the combination (or product) of dose and monomer level does not exceed the levels specified as follows:
Acrylamide = 0.05% dosed at 1 ppm (or equivalent)
Epichlorohydrin = 0.01% dosed at 20 ppm (or equivalent)
Certifications can rely on manufacturers or third parties, as approved by the Department.
BB. Approved Laboratories.
For the purpose of determining compliance with R.61-58.5.B through R.61-58.5.V, R.61-58.5.CC, R.61-58.10.F, R.61-58.11.D, and R.61-58.16.E, samples may be considered only if they have been analyzed by a laboratory approved by the Department, except that measurements for turbidity may be performed by a properly certified water treatment plant operator.
CC. Alternative Analytical Techniques.
With express written permission of the Department, concurred in by the Administrator, an alternative analytical technique may be employed. An alternative technique shall be acceptable only if it is substantially equivalent to the prescribed test in both precision and accuracy as it relates to the determination of compliance with any maximum contaminant level. The use of the alternative analytical technique shall not decrease the frequency of monitoring required by this regulation.
DD. and EE. [Deleted]
Public water systems shall not use bottled water or point-of-use devices to achieve compliance with an established maximum contaminant level. Bottled water or point-of-use devices may be used on a temporary basis to avoid an unreasonable risk to health.
AA. Treatment Techniques.
HISTORY: Amended by State Register Volume 12, Issue No. 11, eff November 25, 1988; State Register Volume 17, Issue No. 8, eff August 27, 1993; State Register Volume 17, Issue No. 12, eff December 24, 1993; State Register Volume 18, Issue No. 11, eff November 25, 1994; State Register Volume 19, Issue No. 7, eff July 28, 1995; State Register Volume 22, Issue No. 6, Part 2, eff June 26, 1998; State Register Volume 24, Issue No. 2, eff February 25, 2000; State Register Volume 25, Issue No. 9, eff September 28, 2001; State Register Volume 26, Issue No. 12, eff December 27, 2002; State Register Volume 27, Issue No. 9, eff September 26, 2003; State Register Volume 28, Issue No. 1, eff January 23, 2004; State Register Volume 30, Issue No. 10, eff October 27, 2006; State Register Volume 32, Issue No. 4, eff April 25, 2008; State Register Volume 38, Issue No. 9, Doc. No. 4469, eff September 26, 2014.