S.C. Code Ann. Regs. 103-475
1. Pre-Installation Inspection.
3. Leak Tests. Every meter shall be leak tested prior to installation.
c. Acceptable Leak Tests.
4. Operating Pressure Limitations.
5. Method of Testing. All tests to determine the accuracy of registration of any gas service meter shall be made with a suitable meter prover.
a. Diaphragm, Displacement, Rotary, and Turbine Meters
(1) Accuracy at Test Points.
| FLOW | ADJUSTED TO WITHIN |
| Check Flow (20% of rated meter capacity) | 98.5%—100.5% |
| Full Flow (Equal to or in excess of operating load requirement) | 98.5%—100.5% |
(2) Actual Accuracy.
The accuracy as determined by averaging the results at the check and open rated flow.
(3) Overall Accuracy.
The accuracy at a check flow and the accuracy at not less than open rated flow shall agree within one percent.
b. Orifice Meters.
Accuracy at test points must be within one-half of one percent plus or minus.
c. Timing Devices.
All recording type meters or associated instruments which have a timing element that serves to record the time at which the measurement occurs must be adjusted as far as practicable so that the timing element is not in error by more than plus or minus five minutes in twenty-four hours.
The tests of any unit of metering equipment shall consist of a comparison of its accuracy with the accuracy of a standard. The ORS will use the applicable provisions of the standards listed in 103-461 as criteria of accepted good practice in testing meters.
All meters and/or associated metering devices, when tested, shall be adjusted as closely as possible to the condition of zero error. All tolerances listed below are to be interpreted as maximum permissible variations from the condition of zero error.
HISTORY: Amended by State Register Volume 32, Issue No. 5, eff May 23, 2008.