25 Pa. Code § 73.16
(b) Absorption areas.
(d) Substitute. When a substitute for aggregate, such as a leaching chamber, large diameter pipe, or other material or device, is used in the absorption area, subsection (b)(1) applies.
| Square Feet of Aggregate Area Per Gallon Per Day | ||
| Average Percolation Rate | All Systems Except | Subsurface Sand |
| Expressed as | Elevated Sand Mounds | Filters and |
| Minute Per Inch | and Subsurface Sand Filters | Elevated Sand Mounds |
| Less than 3.0D | Unsuitable | Unsuitable |
| 3 - 5C | Unsuitable | 1.50AB |
| 6 - 15C | 1.19B | 1.50AB |
| 16 - 30C | (Avg. Perc Rate - 15) x (0.040) + 1.19B | 1.50AB |
| 31 - 45C | (Avg. Perc Rate - 30) x (0.030) + 1.79B | (Avg. Perc Rate - 30) x (0.026) + 1.50AB |
| 46 - 60C | (Avg. Perc Rate - 45) x (0.028) + 2.24B | (Avg. Perc Rate - 45) x (0.022) + 1.89A |
| 61 - 90C | (Avg. Perc Rate - 60) x (0.023) + 2.66A | (Avg. Perc Rate - 60) x (0.020) + 2.22A |
| 91 - 120ACD | Unsuitable | (Avg. Perc Rate - 90) x (0.017) + 2.82A |
| 121 - 150CD | Unsuitable | ((Avg. Perc Rate - 120) x (0.015) + 3.33) (1.05)A |
| 151 - 180CD | Unsuitable | ((Avg. Perc Rate - 150) x (0.014) + 3.78) (1.10)A |
| Greater than 181CD | Unsuitable | Unsuitable |
A Pressure dosing required.
B One third reduction may be permitted for use of an aerobic tank.
C May be considered for experimental or alternate proposals.
D Unsuitable for subsurface sand filters.
(e) Spray fields. Table B shall be used in calculating the square footage of spray fields based on flows determined in Subsection (a). Table B includes allowances for garbage grinders, automatic washing machines, dishwashers and water softeners.
| Soil Characteristics | Slope | Required Spray Field Area (Ft 2) | ||
| Depth To Rock | Depth To Water Table | 3 Bedroom Home | Additional Area Per Bedroom | |
| 16 to 20 inches | 10 to 40 inches | ‹=12% | 40,000 | 10,000 |
| ›12% | 80,000 | 20,000 | ||
| ›40 inches | ‹=12% | 15,000 | 3,750 | |
| ›12% | 30,000 | 7,500 | ||
| ›20 inches | 10 to 20 inches | ‹=12% | 20,000 | 5,000 |
| ›12% | 40,000 | 10,000 | ||
| ›20 inches | ‹=12% | 10,000 | 2,500 | |
| ›12% | 20,000 | 5,000 |
The provisions of this § 73.16 amended under section 9 of the Pennsylvania Sewage Facilities Act (35 P. S. § 750.9); The Clean Streams Law (35 P. S. § § 691.1—691.1001); and section 1920-A of The Administrative Code of 1929 (71 P. S. § 510-20).
The provisions of this § 73.16 adopted January 21, 1983, effective January 22, 1983, 13 Pa.B. 508; amended November 7, 1997, effective November 8, 1997, 27 Pa.B. 5877; corrected November 21, 1997, 27 Pa.B. 6079. Immediately preceding text appears at serial pages (221915) to (221916) and (217317) to (217318).
This section cited in 25 Pa. Code § 71.52 (relating to content requirements—new land development revisions); 25 Pa. Code § 71.63 (relating to retaining tanks); 25 Pa. Code § 72.22 (relating to permit issue); 25 Pa. Code § 73.14 (relating to site investigation); 25 Pa. Code § 73.15 (relating to percolation tests); 25 Pa. Code § 73.54 (relating to subsurface sand filters); 25 Pa. Code § 73.161 (relating to general); and 25 Pa. Code § 73.163 (relating to spray fields).