(2) For demonstrating compliance with particulate standards, testing must be conducted using the following test methods, or alternative methods approved by DEQ:
(a) For wood waste boilers — DEQ Method 5. Results must be corrected to 12% CO2, as follows
(B) As used in paragraph (A):
C(12%CO2) = Particulate matter emission concentration corrected to 12% CO2;
C = Particulate matter emission concentration as measured by Oregon DEQ Method 5; and
% CO2 = Percent CO2 in the exhaust gas, as measured by EPA Method 3 (or equivalent) during each particulate matter test run.
(3) For demonstrating compliance with opacity standards, observations must be made in accordance with EPA Method 9 or continuous opacity monitoring systems certified in accordance with the DEQ Continuous Monitoring Manual.
[NOTE: This rule is included in the State of Oregon Clean Air Act Implementation Plan that EQC adopted under OAR 340-200-0040.]
[NOTE: The DEQ Source Sampling and Continuous Monitoring Manuals are published with OAR 340-200-0035.]
[NOTE: View a PDF of EPA Methods by clicking on “Tables” link below.]
[ED. NOTE: To view attachments referenced in rule text, click here for PDF copy.]
ORS 468.020, 468A.025 & 468A.070
ORS 468A.025 & 468A.070
DEQ 13-2019, amend filed 05/16/2019, effective 05/16/2019
DEQ 7-2015, f. & cert. ef. 4-16-15