(1) An owner and permittee must comply with all release detection requirements for a new or existing UST system or permanently close the UST system by the following schedule:
(a) For UST systems installed before 1965 and for UST systems where the installation date is unknown:
- (A) December 22, 1989, for tanks and suction piping.
- (B) December 22, 1990, for pressurized piping.
- (b) For UST systems installed between 1965 and 1969 — December 22, 1990, for tanks, suction piping and pressurized piping.
(c) For UST systems installed between 1970 and 1974:
- (A) December 22, 1990, for pressurized piping.
- (B) December 22, 1991, for tanks and suction piping.
(d) For UST systems installed between 1975 and 1979:
- (A) December 22, 1990, for pressurized piping.
- (B) December 22, 1992, for tanks and suction piping.
(e) For UST systems installed between 1980 and December 22, 1988:
- (A) December 22, 1990, for pressurized piping.
- (B) December 22, 1993, for tanks and suction piping.
- (f) For tanks, suction piping and pressurized piping, release detection requirements must be met upon date of installation for all new UST systems installed after December 22, 1988.
- (2) An owner and permittee of a new UST system installed after December 22, 1988, must comply with the corrosion protection performance standards for tanks and piping (OAR 340-150-0320 and 340-150-0325) at the time of installation.
- (3) An owner and permittee of an existing UST system installed on or before December 22, 1988, must comply with the requirements for upgrading USTs and piping (OAR 340-150-0560) by no later than December 22, 1998.
- (4) An owner and permittee that does not comply with section (2) or (3) of this rule must decommission the UST system in compliance with the requirements of OAR 340-150-0166 through 340-150-0168 by no later than December 22, 1998.
- (5) An owner and permittee of a hazardous substance UST system (e.g., an UST containing any nonpetroleum regulated substance) installed on or before December 22, 1988, must comply with the release detection requirements of OAR 340-150-0400 and 340-150-0410 until December 22, 1998. After December 22, 1998, an owner and permittee of a hazardous substance UST system must comply with the requirements of 340-150-0420.
- (6) An owner and permittee of a new or existing UST system that does not meet the performance standards in OAR 340-150-0300 or 340-150-0560 may use monthly inventory control and annual tank tightness testing as a release detection method until December 22, 1998. After that date, an owner and permittee must upgrade or permanently close the UST system.
Statutory/Other Authority
ORS 466.706 - 466.835, 466.994 & 466.995
Statutes/Other Implemented
ORS 466.746 & 466.765
History
DEQ 3-2008, f. 2-29-08, cert. ef. 3-10-08
DEQ 6-2003, f. & cert. ef. 2-14-03