(1) Criteria for approval. Construction permits may be issued for seepage trench systems on lots created before January 1, 1974, for sites that meet all the following conditions.
- (a) Groundwater will not be degraded.
- (b) Lot or parcel size will not accommodate standard subsurface system disposal trenches with a design flow of 450 gpd.
- (c) All other requirements for standard subsurface systems can be met.
(2) Design criteria.
- (a) The maximum depth allowed for a seepage trench is 42 inches.
- (b) The seepage trench system must be sized according to the following formula: length of seepage trench = 4 x (length of standard disposal trench) divided by (3 + 2D), where D = depth of drain media below distribution pipe in feet. Maximum depth of drain media (D) is 2 feet.
- (c) The design flow is limited to a maximum of 450 gallons.