(1) The licensee must perform inspection and maintenance checks that include, as a minimum, each of the following at the frequency specified in the license or license application:
- (a) Operability of each aspect of the access control system required by OAR 333-121-0110.
- (b) Functioning of the source position indicator required by OAR 333-121-0150(2).
- (c) Operability of the radiation monitor for radioactive contamination in pool water required by OAR 333-121-0340(2) using a radiation check source, if applicable.
- (d) Operability of the over-pool radiation monitor at underwater irradiators as required by OAR 333-121-0140(2).
- (e) Operability of the product exit monitor required by OAR 333-121-0140(1).
- (f) Operability of the emergency source return control required by OAR 333-121-0150(3).
- (g) Visual inspection of leak-tightness of systems through which pool water circulates.
- (h) Operability of the heat and smoke detectors and extinguisher system required by OAR 333-121-0130, without turning extinguishers on.
- (i) Operability of the means of pool water replenishment required by OAR 333-121-0160(3).
- (j) Operability of the indicators of high and low pool water levels required by OAR 333-121-0160(4).
- (k) Operability of the intrusion alarm required by OAR 333-121-0110(9) if applicable.
- (l) Functioning and wear of the system, mechanisms, and cables used to raise and lower sources.
- (m) Condition of the barrier to prevent products from hitting the sources or source mechanism as required by OAR 333-121-0170.
- (n) Amount of water added to the pool to determine if the pool is leaking.
- (o) Electrical wiring on required safety systems for radiation damage.
- (p) Pool water conductivity measurements and analysis as required by OAR 333-121-0360(2).
- (2) Malfunctions and defects found during inspection and maintenance checks must be repaired within time frames specified in the license or license application.
Statutory/Other Authority
ORS 453.605 – 453.807