Okla. Admin. Code § 748:20-6-10
Chapter 5 of the IRC® 2018 is adopted with the following modifications:
(2) Section R506.2.3 Vapor retarder. This section has been modified to allow for other industry accepted vapor retarders installed according to the manufacturer's specifications. This section has been modified to read: R506.2.3 Vapor retarder. A 6 mil (0.006 inch; 152 micrometers) polyethylene sheeting, other industry accepted vapor retarder products installed per manufacturer specifications or approved vapor retarder with joints lapped not less than 6 inches (152 mm) shall be placed between the concrete floor slab and the base course or the prepared subgrade where no base course exists. Exception: The vapor retarder is not required for the following:
Amended and renumbered from 748:20-5-8 at 39 Ok Reg 2364, eff 9-14-22