Chapter 2 of the Oklahoma adopted NEC® 2023 is adopted with the following modification:
- (1) Section 210.08 (F) Outdoor Outlets. This section has been modified to delete an excepiration date for exception No. 2.. This section has been modified to read: 210.08 (F) Outdoor Outlets. For dwellings, all outdoor outlets , other than those covered in 210.8 (A) , Exception No 1, including outlets installed in the following locations, and supplied by single-phase branch circuits rated 150 volts or less to ground , 50 amperes or less, shall h be supplied with GFCI protection:
- (A) Item 1: Garages that have floors located at or below grade level
- (B) Item 2: Accessory buildings
- (C) Item 3: Boathouses
- (2) If equipment supplied by an outlet covered under the requirements of this section is replaced, the outlet shall be provided with GFCI protection.
- (3) Exceptions:
- (A) Exception No. 1. GFCI protection shall not be required on lighting outlets other than those covered by 210.8(C).
- (B) Exception No. 2. GFCI protection shall not be required for listed HVACequipment.
Amended and renumbered from 748:20-9-6.2 at 38 Ok Reg 2693, eff 9-14-21
Amended at 39 Ok Reg 2370, eff 9-14-22
Amended at 41 Ok Reg, Number 21, effective 9-14-24