- (a) If not provided with an air gap as specified under OAC 310:257-9-15, a dual check valve with an intermediate vent preceded by a screen of not less than 100 mesh to 25.4mm (100 mesh to 1 inch) shall be installed upstream from a carbonating device and downstream from any copper in the water supply line.
- (b) A dual check valve attached to the carbonator need not be of the vented type if an air gap or vented backflow prevention device has been otherwise provided as specified under (a) of this Section.