(a) GAC filter-adsorber. GAC filter-adsorbers utilized by replacing media in an existing filter, capping an existing filter, or by the installation of a new filter-adsorber are allowed. Some of the sand can be replaced in a single media filter or the coal in dual or mixed media filters with GAC.
- (1) When adding GAC to existing filter media, provide a minimum of 15 inches of GAC.
- (2) When using GAC as a single media, provide a total depth of 30 to 36 inches.
- (3) Filter media must be 12 x 40 mesh (effective size of 1.68 to 0.42 mm) or 8 x 30 mesh (effective size of 2.38 to 0.60 mm) with uniformity coefficient of 1.3 - 1.9.
(b) Adsorption with GAC.
(1) A pilot study is required to determine the following design information:
- (A) adsorption isotherm of the contaminants to be removed,
- (B) type, size, and adsorptive characteristics of the GAC to be utilized in the adsorber,
- (C) type, dimensions and configuration of adsorbers, i.e. the number, sequence, and arrangement of the separate GAC contactors,
- (D) location of the adsorber(s) in the water treatment process,
- (E) superficial (approach) velocity,
- (F) minimum empty bed contact time for removal of contaminants to meet regulatory limits,
- (G) bed depth of GAC in adsorber(s), and
- (H) service time of adsorber(s).
- (2) Contactor type and number. Downflow contactors are the only acceptable type for water treatment applications. Where only 2 units are provided, each must be capable of meeting the maximum daily demand. Where more than 2 units are provided, the contactors must be capable of meeting the design capacity with 1 or more units removed from service.
- (3) Media. The carbon media must meet current AWWA Standards for GAC. The particle size must be 12 x 40 US Standard mesh (1.68 x 0.42 mm) with uniformity coefficient of 1.9.
- (4) Backwashing. Provide provisions for backwashing unless the adsorber does not function as a filter and is designed as a replaceable unit. If the source of water for backwashing is the public water supply, proper cross-connection protection must be provided. Disposal of backwash water must be in a manner approved by DEQ.
Added at 18 Ok Reg 1612, eff 6-1-01