- (a) Monitoring required. The incinerator shall have continuous monitoring and recording for waste feed, fuel and combustion gas flows; oxygen and carbon monoxide, and temperature.
- (b) Instrument calibration. Monitoring devices shall be routinely calibrated in accordance with manufacturer's recommendations.
- (c) DEQ may monitor. Incinerators shall have the capability for the DEQ to connect its own monitoring or calibration test equipment.
- (d) Monitoring data retention. Monitoring data shall be maintained for at least two years.
- (e) Excursions. In the event more than thirty excursions from the operating parameters occur within any calendar month, the owner/operator shall shut down operations until such time as repairs are made and documented engineering analysis shows how the cause has been corrected.