Any new VOC storage and/or loading facility may be constructed and any existing VOC storage and/or loading facility may be operated under this Part if the following conditions are met.
- (1) The facility is located in an area designated as unknown or attainment for ozone.
(2) Each storage vessel located at the facility meets one of the following criteria.
- (A) The storage capacity is 19,813 gal (75 m3) or less.
- (B) The storage capacity is greater than 19,813 gal (75 m3) but less than 39,889 gal (151 m3) and the liquid stored has a maximum true vapor pressure less than 2.18 psia (15.0 kPa).
- (C) The storage capacity is greater than or equal to 39,889 gal (151 m3) and the liquid stored has a maximum true vapor pressure less than 0.51 psia (3.5 kPa).
- (3) The facility is designed to have a throughput of 19,998 gal/d (75,700 1/d) or less from the aggregate loading pipes.
- (4) The facility meets the requirements of 252:100-7-60 (a), (b), and (c).
Added at 16 Ok Reg 1767, eff 6-11-99