Okla. Admin. Code § 165:35-17-2
(a) Secondary voltages. The voltage at the utility's point of delivery, as installed for each consumer, shall be maintained within the limits specified in (1) through (4) of this subsection. If a utility adopts any standard voltage not included in the table in (4) of this subsection, it shall advise the Commission that the Commission may establish appropriate voltage limits. Where three-phase service is provided, the utility shall exercise reasonable care to assure that the phase voltages are balanced. The preferred and tolerable voltage ranges conform to the current version of ANSI Standard C84.1, or equivalent ANSI standard as later amended.
| PREFERRED VOLTAGE | TOLERABLE VOLTAGE | |||||
| NORMAL | RANGE | RANGE | ||||
| VOLTAGE | MINIMUM | MAXIMUM | MINIMUM | MAXIMUM | ||
| 120 | 114 | 126 | 110 | |||
| 208Y/120 | 197Y/114 | 218Y/126 | 191Y/110 | 220Y/127 | ||
| 240/120 | 228/114 | 252/126 | 220/110 | 254/127 | ||
| 208 | 197 | 218 | 191 | 220 | ||
| 416Y/240 | 395Y/228 | 436Y/252 | 381Y/220 | 440Y/254 | ||
| 480/240 | 456/228 | 504/252 | 440/220 | 508/254 | ||
| 460Y/265 | 437Y/252 | 483Y/279 | 422Y/244 | 487Y/281 | ||
| 480Y/277 | 456Y/263 | 504/Y291 | 440Y/254 | 508Y/293 | ||
| 440 | 418 | 462 | 403 | 466 | ||
| 480 | 456 | 504 | 440 | 508 | ||
| 832Y/480 | 790Y/456 | 873Y/504 | 762Y/440 | 880Y/508 | ||
| 600 | 570 | 630 | 550 | 655 | ||
(3) Emergency secondary voltages. Voltages outside the limits specified in (4) of this subsection may infrequently occur due to:
(b) Primary voltages. The following limits shall apply where the utility supplies service at primary voltage.
Amended at 10 Ok Reg 2633, eff 6-25-93
Amended at 16 Ok Reg 2237, eff 7-1-99
Amended at 31 Ok Reg 1030, eff 9-12-14