Okla. Admin. Code § 165:26-2-42
Frequency and criteria of inspections and tests
Effective Oct 1, 202441 Ok Reg, Number 23Renumbered from 165:26-3-82 at 23 Ok Reg 2297, eff 7-1-06; Amended at 31 Ok Reg 1010, eff 9-12-14; Amended at 36 Ok Reg 576, eff 8-1-19; Amended at 41 Ok Reg, Number 23, effective 10-1-24Corporation Commission
- (a) All cathodic protection systems must be tested within six(6) months of installation and/or repair, and at least once every three(3) years thereafter by a licensed cathodic protection tester.
- (b) Cathodic protection testing, repair, or three (3) year recertification must be scheduled by submitting the PSTD scheduling form and PSTD staff may be present.
- (c) Every sixty(60) days impressed current cathodic protection systems must be inspected by the owner or owner's designated representative to ensure the equipment is working properly.
- (d) The criteria used to determine whether cathodic protection is adequate must be in accordance with a code of practice developed by a nationally recognized organization, such as the National Association of Corrosion Engineers (NACE) SP0285.
- (e) All personnel performing cathodic protection system testing must have the required license, education, current corrosion certification experience, knowledge and competence to correctly perform testing services in accordance with a certified course and applicable industry standards or codes.