- (a) Aboveground storage tanks exposed to traffic must be resistant to damage from the impact of a motor vehicle by suitable collision barriers. The secondary containment dike may serve as a collision barrier provided that it cannot be penetrated by a motor vehicle.
(b) When guard posts or collision barriers are installed, the following design shall be acceptable:
- (1) They shall be constructed of steel not less than 4 in. (100 millimeters) in diameter and shall be filled with concrete.
- (2) They shall be spaced not more than 4 ft. (1.2 meters) on center.
- (3) They shall be set not less than 3 ft (0.9 meters) deep in a concrete footing of not less than 15-in. (380 millimeters) diameter.
- (4) They shall not be less than three feet (3') above grade and concrete barriers not less than thirty-two inches (32") above grade.
- (5) They shall not be less than five feet (5') from the tank shell.
- (c) Dispensing devices, except those attached to containers, must either be mounted on a concrete island or otherwise protected against collision damage by suitable means and must be securely bolted in place. If located indoors, the dispensing device will be located in a position where it cannot be struck by a vehicle that is out of control descending a ramp or other slope. The installation must be in accordance with the manufacturer's instructions.