(a) The following distances, at a minimum, must be kept around aboveground storage tanks.
- (1) 50 ft (15 meters) from the nearest important building as defined by this Chapter;
- (2) 50 ft (15 meters) from any fuel dispenser;
- (3) 50 ft (15 meters) from the nearest side of a public way; and
- (4) 100 ft (30 meters) from any property line that is or might be built upon, including the opposite side of a public way.
- (b) The distances as set forth in (a) of this may be reduced by 50 percent if the tanks are fire-resistant. The distances as set forth in (a) may be further reduced if the tanks are a fire-protected tank or tanks in vaults as per NFPA 30A-4.3.2.4.
- (c) A variance may be granted for pre-existing facilities where compliance would be difficult and expensive and the current distances between tanks, property lines or dispensers pose no serious threat to people or property.