Okla. Admin. Code § 165:25-2-53
Frequency and criteria of inspections and tests
Effective Oct 1, 202441 Ok Reg, Number 23Added at 21 Ok Reg 2036, eff 7-1-04; Amended at 22 Ok Reg 1730, eff 7-1-05; Amended at 25 Ok Reg 1867, eff 7-1-08; Amended at 31 Ok Reg 1007, eff 9-12-14; Amended at 34 Ok Reg 935, eff 9-11-17; Amended at 36 Ok Reg 551, eff 8-1-19; Amended at 41 Ok Reg, Number 23, effective 10-1-24Corporation Commission
- (a) All cathodic protection systems must be tested within six (6) months of installation and/or repair, and at least once every three (3) years thereafter by a licensed cathodic protection tester.
- (b) Cathodic protection testing, repair, or three (3) year recertification must be scheduled by submitting the PSTD scheduling form and PSTD staff may be present.
- (c) Every sixty (60) days impressed current cathodic protection systems must be inspected by the owner or owner's designated representative to ensure the equipment is working properly.
- (d) The criteria used to determine whether cathodic protection is adequate must be in accordance with a code of practice developed by a nationally recognized organization, such as NACE SP0285.
- (e) All personnel performing cathodic protection system testing must have the required license, education, current corrosion certification, experience, knowledge and competence to correctly perform testing services in accordance with a certified course and applicable industry standards or codes.
Added at 21 Ok Reg 2036, eff 7-1-04
Amended at 22 Ok Reg 1730, eff 7-1-05
Amended at 25 Ok Reg 1867, eff 7-1-08
Amended at 31 Ok Reg 1007, eff 9-12-14
Amended at 34 Ok Reg 935, eff 9-11-17
Amended at 36 Ok Reg 551, eff 8-1-19
Amended at 41 Ok Reg, Number 23, effective 10-1-24