Ohio Rev. Code Ann. § 3781.104
(A) One hundred eighty days after the board of building standards files its rules with the secretary of state and the director of the legislative service commission, as required in section 119.04 of the Revised Code, as required by this section, every existing apartment and condominium building that exceeds seventy-five feet in height, as measured from ground level exclusive of any radio, television, or telephone transmission antennae, or other equipment, chimneys, or equipment associated with the heating or air conditioning system of the building, which did not have an automatic smoke detection system or sprinkler system in conformity with the rules of the board of building standards adopted pursuant to section 3781.10 of the Revised Code, shall have installed and in operation an automatic smoke detection system as follows:
(2) In those portions of a building subject to this division other than dwelling units, detector spacing shall conform to at least one of the following requirements:
(B) As used in this section: