N.Y. Comp. Codes R. & Regs. tit. 6, § 613-2.3
(1) Every facility must provide a method, or combination of methods, of leak detection that:
(4) A facility that cannot implement a method of leak detection that complies with the requirements of this section must take the UST system out of service pursuant to section 613-2.6(a) of this Subpart.
(b) Specific requirements for category 1, 2, and 3 UST systems.
(1) Tanks. USTs must be monitored for leaks as follows:
(2) Piping. Piping that routinely contains petroleum must be monitored for leaks as follows:
(i) Piping installed on or before October 11, 2015 must meet one of the following requirements:
(a) Pressurized piping. Piping that conveys petroleum under pressure must:
(b) Suction piping. Piping that conveys petroleum under suction must either have a line tightness test conducted at least every three years and in accordance with paragraph (d)(2) of this section, or use a monitoring method conducted at weekly intervals in accordance with paragraph (d)(3) of this section. Continuous electronic monitoring satisfies the weekly monitoring requirement. No leak detection is required for suction piping that is shown by the facility to be designed and constructed to meet the following standards:
(ii) Piping installed after October 11, 2015 must meet one of the following requirements:
(iii) All electronic piping monitoring systems must be inspected for operability at monthly intervals.
(c) Methods of leak detection for tanks.
Each method of leak detection for USTs used to meet the requirements of paragraph (b)(1) of this section must be conducted in accordance with the following:
(1) Inventory monitoring. Inventory monitoring must be conducted in the following manner:
(vii) on a daily basis, the facility must calculate the difference between the expected and actual amount of petroleum in the UST. At 10-day intervals, the facility must calculate the sum of the daily differences and compare it to the thresholds in clauses (a) and (b) of this subparagraph to determine if a leak is suspected. A leak is suspected when:
(b) the sum of the daily differences over the ten-day interval exceeds the largest of three-quarters of one percent (0.0075) of:
(2) Manual tank gauging. Manual tank gauging must meet the following requirements:
(iv) a leak is suspected and subject to the requirements of section 613-2.4 of this Subpart if the variation between beginning and ending measurements exceeds the weekly or monthly standards in Table 2 of this subparagraph:
| Table 2: Manual Tank Gauging | |||
| Design Capacity of UST | Minimum Duration of Test | Weekly Standard (One Test) | Monthly Standard (Four-Test Average) |
| 550 gallons or less | 36 hours | 10 gallons | 5 gallons |
| 551-1,000 gallons (when tank diameter is 64") | 44 hours | 9 gallons | 4 gallons |
| 551-1,000 gallons (when tank diameter is 48") | 58 hours | 12 gallons | 6 gallons |
(4) Automatic tank gauging. Equipment for automatic tank gauging which tests for the loss of petroleum must meet the following requirements:
(ii) the test must be performed with the system operating in one of the following modes:
(5) Vapor monitoring. Testing or monitoring for vapors within the soil gas of the excavation zone must meet the following requirements:
(6) Groundwater monitoring. Testing or monitoring for liquids on the groundwater must meet the following requirements:
(7) Interstitial monitoring. Interstitial monitoring between the UST system and a secondary barrier immediately around or beneath it may be used if the system is designed, constructed and installed to detect a leak from any portion of the UST that routinely contains petroleum; and if the system meets one of the requirements set forth in subparagraphs (i) through (iii) of this paragraph:
(ii) for a UST system with a secondary barrier within the excavation zone, the sampling or testing method used can detect a leak between the UST system and the secondary barrier, and the following conditions are met:
(8) Statistical inventory reconciliation. Statistically based testing or monitoring methods must meet the following requirements:
(9) Other methods.
(ii) The department may approve another method if the owner and operator can demonstrate that the method can detect a leak as effectively as any of the methods allowed in paragraphs (4) through (8) of this subdivision.
(d) Methods of leak detection for piping.
Each method of leak detection for piping used to meet the requirements of paragraph (b)(2) of this section must be conducted in accordance with the following:
(3) Alternative leak detection methods. Any of the methods in paragraphs (c)(5) through (8) of this section may be used if they are designed to detect a leak from any portion of the piping that routinely contains petroleum.
(e) Leak detection recordkeeping.
All facilities must maintain records demonstrating compliance with all applicable requirements of this section. These records must meet the following requirements:
(a) Leak detection requirements for all UST systems.